Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 5 — Pressure–Enthalpy Diagram

5.3 — System Capacity and Performance

Every change in operating conditions moves the state points on the P–h diagram. Understanding which direction they move — and why — is how a technician predicts what a service action will do to system capacity, efficiency, and component temperatures before touching anything.

Jump to

5.3.1 — Effect of Condensing Temperature

Condensing temperature (and pressure) is the single most controllable variable in system performance. It is set primarily by the outdoor ambient temperature and the condition of the condenser heat exchanger. On the P–h diagram, raising the condensing temperature shifts the entire high-side horizontal line upward to a higher pressure.

Higher Condensing Temperature
  • High-side pressure increases → Point 2 and Point 3 move up
  • Compression ratio increases → more compressor work (h2−h1 grows)
  • h3 (sat liquid enthalpy) increases → flash gas quality rises
  • Refrigeration effect (h1−h4) decreases
  • COP falls; discharge temperature rises
  • Caused by: dirty condenser, blocked airflow, high ambient, overcharge, non-condensables
Lower Condensing Temperature
  • High-side pressure decreases → Points 2 and 3 move down
  • Compression ratio decreases → less compressor work
  • h3 decreases → less flash gas, more refrigeration effect
  • COP improves; discharge temperature drops
  • Achieved by: clean condenser, adequate condenser airflow, cool ambient, correct charge
📋

Worked Example — Impact of a 10°F Rise in Condensing Temperature (R-410A)

Baseline: Condensing at 130°F, evaporating at 40°F, 15°F SC, 10°F SH.

  • h1 = 124.5 BTU/lb  |  h2 = 149.8 BTU/lb  |  h3 = h4 = 50.5 BTU/lb
  • qevap = 74.0 BTU/lb  |  wcomp = 25.3 BTU/lb  |  COP = 2.92

After condensing temperature rises 10°F to 140°F (dirty condenser, same subcooling):

  • h3 increases to ≈ 52.1 BTU/lb (higher saturated liquid enthalpy at higher pressure)
  • h2 increases to ≈ 155.3 BTU/lb (higher compression ratio increases discharge enthalpy)
  • qevap = 124.5 − 52.1 = 72.4 BTU/lb (down from 74.0 — 2% capacity loss)
  • wcomp = 155.3 − 124.5 = 30.8 BTU/lb (up from 25.3 — 22% more compressor work)
  • COP = 72.4 ÷ 30.8 = 2.35 (down from 2.92 — 19% efficiency loss)

A single 10°F rise in condensing temperature — caused by a moderately dirty condenser coil — costs 19% in efficiency while barely affecting capacity. The compressor is working much harder for nearly the same output. This is why condenser coil cleaning is the highest-value preventive maintenance action on any A/C system.

5.3.2 — Effect of Evaporating Temperature

Evaporating temperature (and pressure) is set by the load on the evaporator and the flow of refrigerant through the metering device. On the P–h diagram, lowering the evaporating temperature shifts the low-side horizontal line downward to a lower pressure.

Lower Evaporating Temperature
  • Low-side pressure decreases → Points 1 and 4 move down
  • Compression ratio increases → more compressor work
  • Refrigerant vapour density at suction decreases → less mass flow per revolution
  • hg (sat vapour enthalpy at low pressure) decreases → suction enthalpy h1 decreases
  • Refrigeration effect per kg may increase slightly, but capacity falls overall (less mass flow)
  • Risk of coil frosting below 32°F (0°C) evaporating temperature
  • Caused by: restricted airflow, dirty evaporator, low charge, restricted metering device
Higher Evaporating Temperature
  • Low-side pressure increases → Points 1 and 4 move up
  • Compression ratio decreases → less compressor work, higher COP
  • Suction vapour density increases → more mass flow per revolution
  • Capacity increases when load is high and airflow is adequate
  • Achieved by: adequate evaporator airflow, clean coil, correct refrigerant charge
⚠️
Low evaporating temperature is a double penalty

When the evaporating temperature drops (e.g., from a dirty evaporator coil or restricted airflow), two bad things happen simultaneously on the P–h diagram: the compression ratio rises (increasing compressor work), AND the suction vapour becomes less dense (reducing mass flow rate). Both effects reduce total system capacity at the same time. This is why diagnosing “low suction pressure” must always start with verifying airflow before suspecting a refrigerant charge problem.

5.3.3 — Effect of Subcooling and Superheat

Subcooling and superheat shift individual state points without changing the operating pressures. Their effects are visible on the P–h diagram as horizontal movements of Points 1 and 3 at their respective pressure levels.

🔻

More Subcooling (Point 3 moves left)

h3 decreases → h4 decreases → refrigeration effect (h1−h4) increases. Flash gas quality decreases → more liquid enters the evaporator. Small improvement in capacity and COP. Maximum benefit is limited by the available condenser surface area and ambient temperature.

🔺

More Superheat (Point 1 moves right)

h1 increases → refrigeration effect appears to increase, but the additional enthalpy is sensible heat gained in the suction line (not in the evaporator). Compressor work also increases because the suction vapour is hotter and less dense. Net effect: no useful capacity gain; discharge temperature rises; compressor is stressed.

Optimal Superheat & Subcooling

Target evaporator superheat of 8–12°F (TXV systems) ensures the compressor receives dry vapour. Target subcooling of 10–20°F ensures liquid delivery to the metering device. Both values at target = system is operating at its rated design point on the P–h diagram.

📋

Worked Example — Improving Subcooling from 5°F to 15°F (R-410A)

A technician finds a system with only 5°F subcooling (bubbles visible in sight glass, suspected low charge). After verifying no leaks and adding refrigerant, subcooling rises to 15°F. Condensing at 130°F, evaporating at 40°F:

Before (5°F SC):

  • Liquid line temp = 125°F → h3 ≈ 54.2 BTU/lb
  • qevap = 124.5 − 54.2 = 70.3 BTU/lb
  • Flash gas quality x4 ≈ (54.2−42.3)÷80.2 = 0.15 (15%)

After (15°F SC):

  • Liquid line temp = 115°F → h3 ≈ 50.5 BTU/lb
  • qevap = 124.5 − 50.5 = 74.0 BTU/lb
  • Flash gas quality x4 ≈ (50.5−42.3)÷80.2 = 0.10 (10%)

Refrigeration effect increased by 5.3% and flash gas dropped by 5 percentage points — purely from restoring proper subcooling.

5.3.4 — Effect of Airflow and Fluid Flow Rates

The P–h diagram shows what happens inside the refrigerant circuit, but the refrigerant can only absorb or reject heat at the rate the air or fluid on the outside of the heat exchangers allows. Inadequate flow is the most common field cause of performance problems.

Flow Problem Affected Component Effect on P–h Diagram Field Symptoms
Low indoor airflow (dirty filter, blocked return, failed blower) Evaporator Evaporating pressure drops; Points 1 & 4 move down; compression ratio increases Low suction pressure, coil frost or ice, high superheat, low supply air temperature differential
Low outdoor airflow (dirty coil, blocked discharge, failed condenser fan) Condenser Condensing pressure rises; Points 2 & 3 move up; COP drops High discharge pressure, HPCO trips, high discharge temperature, low cooling capacity
Low refrigerant mass flow (low charge, restricted metering device) Entire system Low suction pressure (Points 1 & 4 down); high superheat; reduced cycle width Low suction pressure, high superheat, low subcooling, bubbles in sight glass
Excessive indoor airflow Evaporator Evaporating pressure rises slightly; reduced latent removal relative to sensible High supply air temperature (insufficient cooling), reduced dehumidification
💡
Always verify airflow before diagnosing a refrigerant charge problem

Low suction pressure with high superheat can look identical on a gauge set whether caused by a refrigerant undercharge or a dirty evaporator coil. On the P–h diagram, both push Point 1 downward and to the right. Checking filter condition, measuring temperature rise across the evaporator, and confirming blower amperage takes two minutes and can avoid an unnecessary and incorrect refrigerant addition.

5.3.5 — Heat of Compression and Discharge Temperature

The heat of compression (h2−h1) appears on the P–h diagram as the horizontal length of the compression line. Any factor that makes this line longer wastes energy and raises discharge temperature.

⬆️

High Compression Ratio

A large pressure difference between suction and discharge means the compressor must work harder per kg of refrigerant. On the P–h diagram: Point 2 moves further right. Caused by: high condensing pressure (dirty condenser) combined with low suction pressure (restricted airflow or low charge).

🌡️

High Suction Superheat

Hot suction gas entering the compressor has a higher specific volume, reducing mass flow, and starts at a higher enthalpy, making the isentropic compression line start further right. Both increase compressor work per unit of cooling produced and raise discharge temperature.

🔧

Poor Isentropic Efficiency

A worn or damaged compressor with valve leakage, piston ring wear, or bearing friction produces more heat per kg compressed. Point 2 moves further right from the ideal isentrope. Diagnosed by comparing measured discharge enthalpy to the theoretical isentropic value.

🌡️

Discharge Temperature as a Diagnostic Tool

Discharge line temperature (measured at the compressor discharge port, not the condenser inlet) is one of the most useful single-point indicators of system health. A useful rule of thumb:

  • Normal: 150–220°F (66–104°C) — 50–100°F above condensing saturation temperature
  • Above 225°F (107°C): Investigate high compression ratio or excessive superheat
  • Above 250°F (121°C): Risk of oil carbonisation and valve damage — shut down and diagnose
  • Below 150°F (66°C): May indicate liquid flooding back to the compressor (low discharge SH)

On the P–h diagram, discharge temperature is read from the isotherm passing through Point 2. A quick field check: measure the discharge line surface temperature and compare to the condensing saturation temperature. The difference is the discharge superheat — it should be 50–100°F.

5.3.6 — System Load and Design

The building or process load determines how much heat the evaporator must absorb per hour. As load varies with weather, occupancy, and internal gains, the system must adapt while maintaining acceptable temperatures and pressures.

High Load Conditions
  • Evaporating pressure tends to rise (more heat to absorb)
  • Compressor runs longer or at higher capacity (variable speed)
  • Condenser must reject more total heat → discharge pressure rises
  • TXV opens wider to feed more refrigerant → superheat maintained
  • System may struggle to maintain setpoint at design limits
Low Load Conditions
  • Evaporating pressure may rise above design (less heat to absorb)
  • Single-speed systems short-cycle → poor humidity control
  • Variable-speed systems reduce compressor speed to match load
  • Risk of coil freeze-up if evaporating temp drops due to low airflow
  • Subcooling may increase on high side (less heat to reject)
💡
Variable-speed compressors keep the cycle closer to the ideal

A variable-speed (inverter-driven) compressor can modulate between 30% and 120% of rated capacity. At part load, it slows down rather than cycling on and off. On the P–h diagram, this keeps the cycle operating close to its rated state points rather than experiencing the large pressure swings that occur during on/off cycling. The result is more consistent superheat and subcooling, higher average COP, and better humidity control — which is why inverter-driven equipment dominates modern high-efficiency ratings (SEER2 ≥ 18).

5.3.7 — Diagnostic Summary — P–h Diagram Shifts at a Glance

This table connects common field problems to their effect on the cycle plotted on the P–h diagram. Use it to predict what gauge readings and temperatures to expect before connecting tools — and to confirm a diagnosis when readings match the pattern.

Condition Points Affected Direction on P–h Effect on COP Effect on Capacity
Dirty condenser coil 2, 3 (high side) Points 2 & 3 shift UP Decreases Decreases (more flash gas)
Low refrigerant charge 1, 4 (low side) + low SC Points 1 & 4 shift DOWN; Point 3 shifts RIGHT (less SC) Decreases Decreases significantly
Overcharge of refrigerant 2, 3 (high side) Points 2 & 3 shift UP; Point 3 shifts further LEFT (more SC) Decreases Marginal increase then decrease
Restricted evaporator airflow 1, 4 (low side) Points 1 & 4 shift DOWN Decreases Decreases significantly
Increased subcooling (proper charge) 3, 4 Points 3 & 4 shift LEFT (lower enthalpy) Increases Increases
Excessive suction superheat 1 Point 1 shifts RIGHT (higher enthalpy at same pressure) Decreases (more wcomp) Decreases (lower suction density)
Non-condensables in system 2, 3 (high side) Points 2 & 3 shift UP; discharge pressure higher than P–T chart predicts Decreases Decreases
Worn compressor (low ηs) 2 Point 2 shifts RIGHT from isentrope at same pressure (higher h2) Decreases Decreases (less mass flow)
🛠️

Using This Table in the Field

When you connect a manifold gauge set and record suction pressure, discharge pressure, suction line temperature, and liquid line temperature, you have enough data to plot an approximate cycle on the P–h diagram — or at minimum, to locate where the state points are relative to their ideal positions.

  • Plot both pressures as horizontal lines on the diagram
  • Use the P–T chart to find saturation temperatures for each pressure
  • Add superheat (suction line temp minus sat temp) → locate Point 1
  • Add subcooling (sat temp minus liquid line temp) → locate Point 3
  • Read h1, h3 from the diagram; set h4 = h3
  • Calculate qevap and compare to nameplate capacity at those conditions
  • Any deviation from expected values points directly to the table above
Test Your Knowledge
↑ Top