Every HVAC/R circuit is built from conductors that carry current and insulation
that keeps it contained. This lesson covers resistors, conductor materials and
sizing, ampacity rating factors, and the insulation types found in refrigeration
and air conditioning wiring.
Jump to
1.2.1 — Resistors: Selection & Identification
Resistors limit current, divide voltage, and set time constants in electronic control
circuits. While you will rarely replace individual resistors in the field, understanding
how they work and how to read their markings is essential for interpreting control
board schematics and identifying faulty components during board-level troubleshooting.
Factors When Selecting Resistors
Factor
Description
Typical HVAC/R Context
Resistance value (Ω)
Determines current limiting and voltage division. Must match circuit requirements precisely.
Sensor biasing networks; timing RC circuits on control boards
Power rating (W)
Maximum power dissipation without overheating. Underrated resistors discolour, crack, or open.
¼ W and ½ W for low-voltage control circuits; larger for power supplies
Tolerance
Allowable variation from stated value (±1 %, ±5 %, ±10 %). Tighter tolerance = higher cost.
±5 % for general control; ±1 % for precision sensor calibration
Temperature coefficient
Rate of resistance change with temperature (ppm/°C). Low coefficient needed for stable measurements.
Thermistors use high temperature coefficient intentionally for temperature sensing
Resistor Identification Codes
Fixed resistors are marked with their value using colour bands or alphanumeric codes.
Knowing these codes allows a technician to verify a replacement component before installation.
Three-digit code: first two digits = significant figures; third digit = multiplier (number of zeros)
Example: “472” = 47 × 10² = 4 700 Ω (4.7 kΩ)
Four-digit code: three significant figures + multiplier
Example: “1002” = 100 × 10² = 10 000 Ω (10 kΩ)
“R” in the code denotes the decimal point: “4R7” = 4.7 Ω
💡
Special resistors: thermistors and NTC sensors
Many HVAC/R control boards use NTC thermistors (Negative Temperature Coefficient)
as temperature sensors. Their resistance decreases as temperature rises — the opposite
of most materials. When a temperature sensor reads a fault, measure the thermistor resistance
at a known temperature and compare to the manufacturer’s resistance-temperature table before
condemning the control board.
1.2.2 — Conductor Materials & Construction
The conductor is the path current travels. Selecting the right material, size, and
construction for each application is one of the most important decisions in any
electrical installation — it directly affects safety, reliability, and compliance
with the Canadian Electrical Code (CEC).
Conductor Materials
Copper
Lowest resistance of common conductor metals
Excellent mechanical strength and flexibility
Most common material in HVAC/R equipment leads, control wiring, and branch circuits
Easier to terminate without special preparation
Higher cost and weight than aluminum, but preferred for most HVAC/R applications
Aluminum
Higher resistance per unit area than copper — requires a larger gauge for the same ampacity
Lighter and less expensive; used for large feeders and service entrance conductors
Prone to oxide layer formation at terminations, increasing resistance over time
Requires anti-oxidant compound and CU/AL-rated terminals
Not used inside equipment; limited to building wiring feeders
Solid vs. Stranded Construction
Solid Conductor
Single wire of the full cross-sectional area
Maintains shape after bending — easier to route through conduit
Common in branch circuit building wiring (12 AWG and 14 AWG NMD-90)
Not suitable where repeated flexing occurs
Stranded Conductor
Multiple small wires twisted together to form one conductor
Highly flexible — resists fatigue from repeated bending
Used for motor leads, equipment wiring, and flexible conduit connections
Slightly larger overall diameter than equivalent solid conductor
American Wire Gauge (AWG)
AWG is the standard sizing system for conductors in North America. The gauge number
runs inversely to size — a smaller number means a larger,
heavier conductor with higher ampacity and lower resistance per foot.
AWG
Approx. Diameter (mm)
Ampacity at 60°C (copper)
Common HVAC/R Use
18
1.02
7 A
Thermostat cable, low-voltage control wiring (24 VAC)
14
1.63
15 A
15 A branch circuits; small single-phase equipment
12
2.05
20 A
20 A branch circuits; typical residential condensing unit circuits
10
2.59
30 A
30 A circuits; larger single-phase A/C and heat pump units
8
3.26
40 A
Electric heating, larger single-phase compressors
6
4.11
55 A
Larger commercial single-phase and small three-phase loads
4
5.19
70 A
Three-phase commercial equipment, large air handlers
Ampacity values are for copper conductors in free air at 30 °C ambient, 60 °C insulation rating.
Always apply CEC derating factors for conduit fill, high ambient temperature, and continuous loads.
1.2.3 — Conductor Ampacity Rating
Ampacity is the maximum continuous current a conductor can carry
without exceeding the temperature rating of its insulation. The published ampacity
tables in the Canadian Electrical Code assume standard conditions; real installations
often require derating (reducing the allowable current) to account for adverse conditions.
Factors That Determine Ampacity
Conductor material: Copper has lower resistance and higher ampacity than aluminum of the same gauge.
Conductor size (AWG or mm²): Larger cross-sectional area carries more current with less heat generation per unit length.
Insulation type and temperature rating: 60 °C, 75 °C, and 90 °C ratings; higher-rated insulation permits higher ampacity at a given temperature.
Ambient temperature: Tables assume 30 °C ambient. In hot equipment rooms or rooftop installations where ambient may reach 40–50 °C, ampacity must be reduced.
Number of current-carrying conductors in a raceway or cable: Grouped conductors cannot dissipate heat as easily; ampacity is derated when more than three conductors share a conduit.
Continuous load factor: The CEC requires conductors supplying continuous loads (operating ≥3 hours) to be sized at 125 % of the load current.
🔧
Worked Example — Ampacity Derating for Conduit Fill
A rooftop unit requires three 10 AWG copper THHN conductors (90 °C rated, table ampacity = 40 A)
run in the same conduit alongside three other current-carrying conductors from a different circuit —
six conductors total.
CEC Table 5C derating factor for 7–9 conductors in a raceway: 70 %
(for 4–6 conductors: 80 %).
Derated Ampacity
40 A × 0.80 = 32 A (6 conductors in raceway)
The rooftop unit has a minimum circuit ampacity (MCA) of 28 A. With a derated ampacity
of 32 A, the 10 AWG conductor still meets requirements. If the MCA were 35 A, a larger
conductor (8 AWG, table ampacity 55 A → derated 44 A) would be required.
Lesson: Always check conduit fill when multiple circuits share the same
raceway. This is a common oversight on HVAC/R rooftop installations where conduit from
several units converges at the service disconnect.
⚠️
Motor conductor sizing rule
For HVAC/R motor branch circuits, the conductor must be sized for at least
125 % of the motor’s FLA (CEC Rule 28-106). This is separate from
the overcurrent device rating. Example: a compressor with 18 A FLA requires conductors
rated for at least 18 × 1.25 = 22.5 A — select 10 AWG
(30 A at 60 °C), not 12 AWG.
1.2.4 — Wire Insulating Materials
Insulation serves two purposes: it prevents current from taking unintended paths
(shock, short circuit) and it protects the conductor from its environment
(moisture, oil, heat, and mechanical damage). Selecting the correct insulation type
is as important as selecting the correct conductor size.
Key Properties of Insulating Materials
Dielectric strength: Resistance to electrical breakdown under high voltage. Measured in volts per millimetre (V/mm); must exceed the circuit voltage by a large safety margin.
Temperature rating: Maximum continuous operating temperature. Using a conductor rated below the actual operating temperature degrades insulation and creates a fire hazard.
Moisture and chemical resistance: Critical in refrigeration plant rooms, outdoor condensing unit wiring, and areas exposed to refrigerant oil or cleaning chemicals.
Flexibility: Required for motor leads, equipment wiring, and any location where conductors are flexed during installation or service.
Mechanical (abrasion) resistance: Conductors routed through sheet metal knockouts, conduit fittings, or equipment enclosures need durable insulation that resists cutting.
Common Wire Types in HVAC/R
Wire Type / Designation
Temp. Rating
Characteristics
Typical HVAC/R Application
TW
60 °C
Thermoplastic insulation; moisture-resistant; basic building wire
Branch circuit wiring in dry locations; older installations
THW
75 °C
Thermoplastic, heat and moisture resistant; higher ampacity than TW at same gauge
Conduit wiring in damp or wet locations; equipment feeders
THHN / THWN
90 °C (dry) / 75 °C (wet)
Nylon outer jacket over PVC insulation; thin, flexible, high temperature rating; very common
Standard choice for conduit wiring in new HVAC/R installations
XHHW
90 °C (dry & wet)
Cross-linked polyethylene (XLPE) insulation; excellent moisture, heat, and chemical resistance
Outdoor and wet-location feeders; industrial refrigeration wiring
24 VAC control circuits: thermostat, zone valves, heat anticipators
Equipment lead / appliance wire
105 °C and above
Flexible, heat-resistant (often fibreglass or silicone insulated); rated for high-temperature environments
Factory wiring inside equipment near compressors, heater elements, and motor terminals
FEP / Silicone high-temp
200 °C+
Fluoropolymer or silicone rubber; extreme temperature resistance; chemically inert
Wiring adjacent to electric defrost heaters, high-temperature furnace controls
🔧
Worked Example — Insulation Selection for a Rooftop Unit
A 5-ton rooftop unit (208/230 V, 3-phase) is being wired with conductors run
in rigid conduit from the rooftop disconnect to the unit. The conduit is exposed
on the roof surface where summer ambient temperatures can reach 45 °C,
and rain enters the conduit hub during storms.
Wet location: THWN or XHHW rated; eliminates standard TW or THHN (dry rating only in wet).
High ambient (45 °C): Applies a temperature derating factor to 75 °C-rated wire. XHHW at 90 °C wet has no derating until 40 °C — a slight derating applies but retains more margin.
Selection: XHHW-2 (90 °C wet) is the preferred choice for this application — it handles both moisture and elevated ambient temperature without a significant ampacity penalty.
The equipment leads inside the unit (near the compressor and heater) remain
the factory-installed high-temperature appliance wire, which is not replaced in the field.
CEC ampacity tables list values for 60 °C, 75 °C, and 90 °C rated conductors.
A 10 AWG copper conductor has a 60 °C ampacity of 30 A, a 75 °C ampacity of 35 A,
and a 90 °C ampacity of 40 A. Always use the column matching the actual insulation
temperature rating of the installed conductor — not the highest column available.