Unit 4 — Electrical Fundamentals
Section 1 — Introduction to Electricity

1.4 — Relays, Switches, Contactors & Transformers

These four component families form the backbone of every HVAC/R control circuit. Switches sense conditions and pass signals; relays amplify those signals into control actions; contactors execute those actions at load voltage and current; and transformers supply the low-voltage power that makes it all possible.

Jump to

1.4.1 — Switches

A switch is any device that opens or closes a circuit to control current flow. In HVAC/R, switches range from simple manual toggles to sophisticated automatic sensing devices that respond to pressure, temperature, or fluid flow. Every switch is described by two key characteristics: how it is actuated (what makes it change state) and what its normal position is (normally-open or normally-closed when the actuator is at rest).

Normally-Open (NO) vs Normally-Closed (NC)

Normally-Open (NO)
  • Contacts are open (circuit broken) at rest
  • Close (complete the circuit) when the actuator is activated
  • Examples: low-pressure switch on a pump-down circuit; thermostat cooling contact
  • A failed-open NO switch keeps the load off — safer for most control applications
Normally-Closed (NC)
  • Contacts are closed (circuit complete) at rest
  • Open (break the circuit) when the actuator is activated
  • Examples: high-pressure safety switch; low-pressure safety switch; thermal overload
  • A failed-open NC safety switch shuts down the equipment — the fail-safe design

Switch Types in HVAC/R

Switch Type Actuated By Normal Position Typical Application
Toggle / selector switch Manual (hand) Latched in last position System on/off; fan speed selection; heat/cool/auto mode selector
Disconnect switch Manual (hand) Operator-set Isolates equipment from power for servicing; required within sight of equipment (CEC)
High-pressure switch (HPS) Refrigerant discharge pressure NC — opens on high pressure Safety: stops compressor before discharge pressure reaches dangerous levels
Low-pressure switch (LPS) Refrigerant suction pressure NC (safety) or NO (operating) Safety: stops compressor on low suction (loss of charge). Operating: controls pump-down sequence
Thermostat Temperature (bimetal, electronic sensor) Varies by stage (heating NO / cooling NC or vice versa) Space temperature control; freeze stat; coil temperature limit; anti-short-cycle timer
Flow switch Air or fluid velocity / differential pressure NO — closes when flow is established Chilled-water system interlock (compressor cannot run without water flow); evaporator fan interlock
Float switch Liquid level NO or NC depending on design Condensate pan overflow safety; refrigerant liquid level in surge drum
🔧

Worked Example — Diagnosing a High-Pressure Switch Trip

A split-system condensing unit shuts down and the high-pressure switch (HPS) is found open. The technician’s diagnostic sequence:

  1. Measure discharge pressure with gauges — confirm it exceeded the HPS set point (e.g., 400 psig for R-410A).
  2. Identify the cause of elevated head pressure: dirty condenser coil, failed condenser fan motor, or blocked airflow.
  3. Correct the cause before resetting the HPS. On a manual-reset HPS, depress the reset button only after discharge pressure drops below the cut-in set point.
  4. Run the system and confirm head pressure returns to normal operating range (350–390 psig at 95 °F ambient).
  5. If the HPS trips again immediately after reset, the root cause has not been corrected — do not repeatedly reset.

1.4.2 — Relays

A relay is an electrically operated switch. A small current through the coil creates a magnetic field that moves an armature, changing the state of one or more sets of contacts. This allows a low-power signal (e.g., a 24 V thermostat output) to switch a higher-power load indirectly — without any electrical connection between the control circuit and the load circuit.

Contact Arrangements

Designation Full Name Contacts Function
SPST-NO Single Pole, Single Throw — Normally Open 1 set, open at rest Simple on/off switching of one circuit; closes when coil energises
SPST-NC Single Pole, Single Throw — Normally Closed 1 set, closed at rest Simple on/off where energising the coil breaks (opens) the circuit
SPDT Single Pole, Double Throw 1 common + 1 NO + 1 NC Switches one circuit between two destinations; used for reversing, alternating, or changeover logic
DPDT Double Pole, Double Throw 2 commons + 2 NO + 2 NC Two independent SPDT switching actions simultaneously; common in reversing valve control and staging applications

Key Relay Ratings

Common Relay Applications in HVAC/R

❄️

Defrost Relay

Shifts the system from cooling to defrost mode on a time or temperature signal. Typically DPDT: one set of contacts energises the defrost heater; the other interrupts the compressor or reversing valve.

🌡️

Staging Relay

Sequences multiple compressors, heater stages, or fan speeds to match load. Each relay acts as a lockout or enable for the next stage, preventing all loads from energising simultaneously.

🔔

Alarm Relay

Latches when a fault is detected (pressure trip, temperature limit) and powers an alarm indicator or BAS point. Requires a manual reset at the panel to clear, ensuring the fault is acknowledged before restart.

⏱️

Time-Delay Relay

Introduces a timed delay before contacts change state (on-delay or off-delay). Used for anti-short-cycle protection (prevents compressor restart for 5 minutes after shutdown) and fan-delay logic.

💡
Testing a relay in the field

With power off: measure coil resistance (should match specification, typically 100–1 000 Ω for 24 VAC coils). Measure contact continuity: NC contacts should read 0 Ω, NO contacts should read open (O.L. on a digital meter). With power on: apply rated voltage to the coil and verify contacts change state. A relay that hums but does not pull in has insufficient coil voltage or a seized armature.

1.4.3 — Contactors

A contactor is a heavy-duty relay designed specifically for switching high-current loads: compressor motors, condenser fan motors, and large resistance heaters. While the operating principle is identical to a relay, the construction is substantially more robust to handle the arc energy and mechanical wear generated by high-current switching.

Relay vs Contactor — Key Differences

Feature Control Relay Contactor
Contact current rating Typically 5–30 A Typically 25–400 A (matched to motor FLA)
Contact type Small silver alloy contacts; light-duty arcing Heavy silver cadmium oxide or silver alloy; arc-suppression chambers
Mechanical life 1–10 million operations 1–5 million operations (lower due to higher energy per switching event)
Auxiliary contacts All contacts typically the same rating Separate power contacts (high current) and auxiliary contacts (low current) for interlocking and indication
Coil voltage 24 VAC, 24 VDC, 120 VAC common Almost always 24 VAC in HVAC/R; coil driven by thermostat control circuit
Replacement indicator Replace when contacts pit or coil fails Replace when contact pitting exceeds 1/32 in. depth or contacts weld; inspect at each PM visit

Contactor Construction

🔧

Worked Example — Contactor Voltage Drop Test

A compressor is running at reduced capacity. The technician suspects the contactor contacts are pitted. With the system running at full load:

  1. Set the voltmeter to AC voltage. Place one probe on the line (supply) side of the contactor and the other probe on the load side of the same phase.
  2. Read the voltage drop across the closed contacts. Acceptable: <2 V. This reading = 1.8 V (acceptable).
  3. Repeat for each pole. Phase B reads 8.5 V — well above the 2 V limit.
  4. Shut down and lock out the unit. Inspect Phase B contacts: significant pitting and carbon deposits confirmed.
  5. Replace the contactor. After replacement, voltage drop on all three phases: <0.5 V. Compressor current returns to nameplate FLA.

An 8.5 V drop at 18 A represents a power loss of 8.5 × 18 = 153 W dissipated as heat in the contactor — enough to discolour the contact housing and eventually destroy the contactor and wiring insulation nearby.

1.4.4 — Transformers

A transformer transfers electrical energy between two circuits using electromagnetic induction, with no direct electrical connection between primary and secondary. In HVAC/R, the most common transformer steps line voltage (120–600 V) down to 24 VAC to power thermostats, contactor coils, relay coils, and electronic control boards.

Transformer Types

🔻

Control Transformer

The most common type in HVAC/R. Steps 120 V, 208 V, or 240 V down to 24 VAC for thermostats and control circuits. Housed inside the equipment or in a separate enclosure. VA-rated to match the total coil burden of the circuit it feeds.

🔒

Isolation Transformer

Primary and secondary are wound to the same voltage, but the secondary is completely isolated from earth ground. Used for safety (eliminates shock path through earth) and to reduce electrical noise interference in sensitive electronic equipment.

↕️

Autotransformer

Uses a single tapped winding rather than separate primary and secondary windings. More efficient and compact than a two-winding transformer, but provides no galvanic isolation. Used in some motor-starting applications and voltage adjustment.

Operating Principle & Turns Ratio

An alternating current in the primary winding creates a changing magnetic flux in the core. This flux induces a voltage in the secondary winding proportional to the ratio of turns:

Turns Ratio

Vprimary / Vsecondary = Nprimary / Nsecondary

A 240 V primary / 24 V secondary transformer has a turns ratio of 10:1 — the primary has 10 times as many turns as the secondary.

By the law of conservation of energy (ignoring losses), the power in equals the power out, so if voltage steps down, current steps up proportionally:

Current Relationship

Iprimary / Isecondary = Nsecondary / Nprimary

A step-down transformer draws less current on the primary (high-voltage) side than it delivers on the secondary (low-voltage) side. Example: 40 VA at 240 V primary = 0.17 A; 40 VA at 24 V secondary = 1.67 A.

VA Rating & Burden Calculation

The VA (volt-ampere) rating of a transformer is the maximum load it can supply continuously. In a control circuit, the burden is the total VA drawn by all loads connected to the secondary: contactor coils, relay coils, and any electronic accessories.

🔧

Worked Example — Control Transformer VA Sizing

A rooftop unit’s 24 VAC control circuit must power the following loads:

LoadQuantityVA EachTotal VA
Compressor contactor coil112 VA12 VA
Condenser fan contactor coil18 VA8 VA
Control relay coils34 VA12 VA
Electronic thermostat / controller110 VA10 VA
Total burden42 VA

A standard 40 VA control transformer would be undersized for this circuit. The correct selection is a 50 VA transformer (next standard size above 42 VA), providing an 18 % margin above the calculated burden.

Symptom of an undersized transformer: the control transformer runs hot, the 24 V output sags below 22 V under full load, contactors chatter or fail to hold in, and the transformer secondary fuse (if fitted) blows repeatedly. Always measure 24 V at the contactor coil terminals — not just at the transformer secondary — to detect excessive voltage drop.

Transformer Protection

⚠️
Common installation error: sharing one transformer across multiple systems

Field installers sometimes wire two roof-top units to a single control transformer to save cost. If both systems call simultaneously, the combined burden may exceed the transformer VA rating, causing the secondary voltage to collapse and both systems to shut down on low-voltage. Always provide a dedicated control transformer for each system unless the manufacturer explicitly allows a shared supply and the VA budget has been calculated.

Test Your Knowledge
↑ Top