These four component families form the backbone of every HVAC/R control circuit.
Switches sense conditions and pass signals; relays amplify those signals into
control actions; contactors execute those actions at load voltage and current;
and transformers supply the low-voltage power that makes it all possible.
Jump to
1.4.1 — Switches
A switch is any device that opens or closes a circuit to control current flow.
In HVAC/R, switches range from simple manual toggles to sophisticated automatic
sensing devices that respond to pressure, temperature, or fluid flow.
Every switch is described by two key characteristics: how it is actuated
(what makes it change state) and what its normal position is
(normally-open or normally-closed when the actuator is at rest).
Normally-Open (NO) vs Normally-Closed (NC)
Normally-Open (NO)
Contacts are open (circuit broken) at rest
Close (complete the circuit) when the actuator is activated
Examples: low-pressure switch on a pump-down circuit; thermostat cooling contact
A failed-open NO switch keeps the load off — safer for most control applications
Normally-Closed (NC)
Contacts are closed (circuit complete) at rest
Open (break the circuit) when the actuator is activated
A failed-open NC safety switch shuts down the equipment — the fail-safe design
Switch Types in HVAC/R
Switch Type
Actuated By
Normal Position
Typical Application
Toggle / selector switch
Manual (hand)
Latched in last position
System on/off; fan speed selection; heat/cool/auto mode selector
Disconnect switch
Manual (hand)
Operator-set
Isolates equipment from power for servicing; required within sight of equipment (CEC)
High-pressure switch (HPS)
Refrigerant discharge pressure
NC — opens on high pressure
Safety: stops compressor before discharge pressure reaches dangerous levels
Low-pressure switch (LPS)
Refrigerant suction pressure
NC (safety) or NO (operating)
Safety: stops compressor on low suction (loss of charge). Operating: controls pump-down sequence
Thermostat
Temperature (bimetal, electronic sensor)
Varies by stage (heating NO / cooling NC or vice versa)
Space temperature control; freeze stat; coil temperature limit; anti-short-cycle timer
Flow switch
Air or fluid velocity / differential pressure
NO — closes when flow is established
Chilled-water system interlock (compressor cannot run without water flow); evaporator fan interlock
Float switch
Liquid level
NO or NC depending on design
Condensate pan overflow safety; refrigerant liquid level in surge drum
🔧
Worked Example — Diagnosing a High-Pressure Switch Trip
A split-system condensing unit shuts down and the high-pressure switch (HPS) is
found open. The technician’s diagnostic sequence:
Measure discharge pressure with gauges — confirm it exceeded the HPS set point (e.g., 400 psig for R-410A).
Identify the cause of elevated head pressure: dirty condenser coil, failed condenser fan motor, or blocked airflow.
Correct the cause before resetting the HPS. On a manual-reset HPS, depress the reset button only after discharge pressure drops below the cut-in set point.
Run the system and confirm head pressure returns to normal operating range (350–390 psig at 95 °F ambient).
If the HPS trips again immediately after reset, the root cause has not been corrected — do not repeatedly reset.
1.4.2 — Relays
A relay is an electrically operated switch. A small current through the
coil creates a magnetic field that moves an armature, changing
the state of one or more sets of contacts. This allows a
low-power signal (e.g., a 24 V thermostat output) to switch a higher-power load
indirectly — without any electrical connection between the control circuit
and the load circuit.
Contact Arrangements
Designation
Full Name
Contacts
Function
SPST-NO
Single Pole, Single Throw — Normally Open
1 set, open at rest
Simple on/off switching of one circuit; closes when coil energises
SPST-NC
Single Pole, Single Throw — Normally Closed
1 set, closed at rest
Simple on/off where energising the coil breaks (opens) the circuit
SPDT
Single Pole, Double Throw
1 common + 1 NO + 1 NC
Switches one circuit between two destinations; used for reversing, alternating, or changeover logic
DPDT
Double Pole, Double Throw
2 commons + 2 NO + 2 NC
Two independent SPDT switching actions simultaneously; common in reversing valve control and staging applications
Key Relay Ratings
Coil voltage: Must match the control circuit voltage exactly — common values are 24 VAC, 120 VAC, 240 VAC, and 24 VDC. Applying the wrong voltage destroys the coil.
Contact current rating: Maximum continuous current the contacts can switch. Exceeding this rating causes arcing, pitting, and welded contacts.
Contact voltage rating: Maximum voltage across the open contacts. Must exceed the circuit voltage being switched.
Coil resistance: Used to verify coil integrity. Measure with a multimeter — an open coil reads infinite resistance; a shorted coil reads near zero and the relay draws excessive current.
Common Relay Applications in HVAC/R
❄️
Defrost Relay
Shifts the system from cooling to defrost mode on a time or temperature signal. Typically DPDT: one set of contacts energises the defrost heater; the other interrupts the compressor or reversing valve.
🌡️
Staging Relay
Sequences multiple compressors, heater stages, or fan speeds to match load. Each relay acts as a lockout or enable for the next stage, preventing all loads from energising simultaneously.
🔔
Alarm Relay
Latches when a fault is detected (pressure trip, temperature limit) and powers an alarm indicator or BAS point. Requires a manual reset at the panel to clear, ensuring the fault is acknowledged before restart.
⏱️
Time-Delay Relay
Introduces a timed delay before contacts change state (on-delay or off-delay). Used for anti-short-cycle protection (prevents compressor restart for 5 minutes after shutdown) and fan-delay logic.
💡
Testing a relay in the field
With power off: measure coil resistance (should match specification, typically 100–1 000 Ω for 24 VAC coils).
Measure contact continuity: NC contacts should read 0 Ω, NO contacts should read open (O.L. on a digital meter).
With power on: apply rated voltage to the coil and verify contacts change state.
A relay that hums but does not pull in has insufficient coil voltage or a seized armature.
1.4.3 — Contactors
A contactor is a heavy-duty relay designed specifically for switching high-current
loads: compressor motors, condenser fan motors, and large resistance heaters.
While the operating principle is identical to a relay, the construction is
substantially more robust to handle the arc energy and mechanical wear generated
by high-current switching.
Relay vs Contactor — Key Differences
Feature
Control Relay
Contactor
Contact current rating
Typically 5–30 A
Typically 25–400 A (matched to motor FLA)
Contact type
Small silver alloy contacts; light-duty arcing
Heavy silver cadmium oxide or silver alloy; arc-suppression chambers
Mechanical life
1–10 million operations
1–5 million operations (lower due to higher energy per switching event)
Auxiliary contacts
All contacts typically the same rating
Separate power contacts (high current) and auxiliary contacts (low current) for interlocking and indication
Coil voltage
24 VAC, 24 VDC, 120 VAC common
Almost always 24 VAC in HVAC/R; coil driven by thermostat control circuit
Replacement indicator
Replace when contacts pit or coil fails
Replace when contact pitting exceeds 1/32 in. depth or contacts weld; inspect at each PM visit
Contactor Construction
Main power contacts: Carry the full motor current. Arranged as 2-pole (single-phase) or 3-pole (three-phase). Contacts must be clean and flat — pitted or burned contacts cause voltage drop and motor overheating.
Auxiliary contacts: Low-current contacts used for control interlocking (e.g., a normally-open auxiliary contact that confirms the contactor has pulled in before allowing the next stage to energise).
Coil and armature: The 24 VAC coil pulls the movable armature against the stationary core, bridging the contacts. A coil that hums loudly has a loose or dirty armature face — clean or replace.
Arc suppression: Metal arc chutes or magnetic blowout coils extinguish the arc that forms when contacts break under load, preventing contact erosion and radio-frequency interference.
🔧
Worked Example — Contactor Voltage Drop Test
A compressor is running at reduced capacity. The technician suspects the contactor
contacts are pitted. With the system running at full load:
Set the voltmeter to AC voltage. Place one probe on the line (supply) side of the contactor and the other probe on the load side of the same phase.
Read the voltage drop across the closed contacts. Acceptable: <2 V. This reading = 1.8 V (acceptable).
Repeat for each pole. Phase B reads 8.5 V — well above the 2 V limit.
Shut down and lock out the unit. Inspect Phase B contacts: significant pitting and carbon deposits confirmed.
Replace the contactor. After replacement, voltage drop on all three phases: <0.5 V. Compressor current returns to nameplate FLA.
An 8.5 V drop at 18 A represents a power loss of 8.5 × 18 = 153 W
dissipated as heat in the contactor — enough to discolour the contact housing
and eventually destroy the contactor and wiring insulation nearby.
1.4.4 — Transformers
A transformer transfers electrical energy between two circuits using
electromagnetic induction, with no direct electrical connection between primary
and secondary. In HVAC/R, the most common transformer steps line voltage
(120–600 V) down to 24 VAC to power thermostats, contactor
coils, relay coils, and electronic control boards.
Transformer Types
🔻
Control Transformer
The most common type in HVAC/R. Steps 120 V, 208 V, or 240 V down to 24 VAC for thermostats and control circuits. Housed inside the equipment or in a separate enclosure. VA-rated to match the total coil burden of the circuit it feeds.
🔒
Isolation Transformer
Primary and secondary are wound to the same voltage, but the secondary is completely isolated from earth ground. Used for safety (eliminates shock path through earth) and to reduce electrical noise interference in sensitive electronic equipment.
↕️
Autotransformer
Uses a single tapped winding rather than separate primary and secondary windings. More efficient and compact than a two-winding transformer, but provides no galvanic isolation. Used in some motor-starting applications and voltage adjustment.
Operating Principle & Turns Ratio
An alternating current in the primary winding creates a changing
magnetic flux in the core. This flux induces a voltage in the
secondary winding proportional to the ratio of turns:
Turns Ratio
Vprimary / Vsecondary = Nprimary / Nsecondary
A 240 V primary / 24 V secondary transformer has a turns ratio of 10:1 — the primary has 10 times as many turns as the secondary.
By the law of conservation of energy (ignoring losses), the power in equals the
power out, so if voltage steps down, current steps up proportionally:
Current Relationship
Iprimary / Isecondary = Nsecondary / Nprimary
A step-down transformer draws less current on the primary (high-voltage) side than it delivers on the secondary (low-voltage) side. Example: 40 VA at 240 V primary = 0.17 A; 40 VA at 24 V secondary = 1.67 A.
VA Rating & Burden Calculation
The VA (volt-ampere) rating of a transformer is the maximum load it can supply
continuously. In a control circuit, the burden is the total VA drawn by
all loads connected to the secondary: contactor coils, relay coils, and any
electronic accessories.
🔧
Worked Example — Control Transformer VA Sizing
A rooftop unit’s 24 VAC control circuit must power the following loads:
Load
Quantity
VA Each
Total VA
Compressor contactor coil
1
12 VA
12 VA
Condenser fan contactor coil
1
8 VA
8 VA
Control relay coils
3
4 VA
12 VA
Electronic thermostat / controller
1
10 VA
10 VA
Total burden
42 VA
A standard 40 VA control transformer would be undersized for this circuit.
The correct selection is a 50 VA transformer (next standard size above 42 VA),
providing an 18 % margin above the calculated burden.
Symptom of an undersized transformer: the control transformer runs
hot, the 24 V output sags below 22 V under full load, contactors chatter or fail to
hold in, and the transformer secondary fuse (if fitted) blows repeatedly.
Always measure 24 V at the contactor coil terminals — not just at the
transformer secondary — to detect excessive voltage drop.
Transformer Protection
Secondary fuse or breaker: Many control transformers include a secondary fuse (typically 3 A for a 40–75 VA / 24 V transformer). This fuse protects the transformer windings from a short circuit on the 24 V circuit — for example, a shorted thermostat wire touching the equipment chassis.
Primary protection: The transformer primary is protected by the branch circuit fuse or breaker on the line-voltage side.
Thermal protection: Class 2 control transformers include internal thermal protection that opens the circuit if the core overheats from an overloaded or shorted secondary.
Replacement: Replace a blown secondary fuse only after identifying and correcting the short circuit; a second fuse will blow immediately if the fault remains. Use only the rated fuse type and amperage.
⚠️
Common installation error: sharing one transformer across multiple systems
Field installers sometimes wire two roof-top units to a single control transformer to save cost.
If both systems call simultaneously, the combined burden may exceed the transformer VA rating,
causing the secondary voltage to collapse and both systems to shut down on low-voltage. Always
provide a dedicated control transformer for each system unless the manufacturer explicitly
allows a shared supply and the VA budget has been calculated.