Motor current, temperature, efficiency, and power factor all shift in predictable
ways when mechanical load or supply voltage changes. Understanding these relationships
allows technicians to diagnose overloads, voltage problems, and sizing issues from
measured electrical quantities alone.
Jump to
2.6.1 — Effects of Load Changes
An induction motor is a self-regulating device: it draws exactly the current
needed to produce the torque required by its mechanical load. As the shaft load
increases, slip increases, the rotating magnetic field induces more rotor current,
and the stator automatically draws more current from the supply. Every electrical
and thermal parameter shifts as a result.
⇧Increased Load
Shaft speed↓ Decreases
Slip↑ Increases
Stator current (amperes)↑ Increases
Input power (watts)↑ Increases
Winding temperature↑ Increases
Efficiency↑ Improves (to peak)
Power factor↑ Improves (to peak)
⇩Decreased Load
Shaft speed↑ Increases (toward Ns)
Slip↓ Decreases
Stator current (amperes)↓ Decreases
Input power (watts)↓ Decreases
Winding temperature↓ Decreases
Efficiency↓ Drops (fixed losses dominate)
Power factor↓ Drops significantly
💡
No-load current is not zero
Even with no mechanical load on the shaft, a motor draws 30–60% of its
full-load current. This magnetising current creates the rotating magnetic field
and is largely reactive (lagging). It is why lightly loaded or no-load motors
have very poor power factor. Always measure and record running current under
actual operating conditions — not at startup or no-load.
Overload Relay Sizing
Overload relays protect the motor from sustained over-current caused by
overloading. They must be sized to the motor’s actual full-load
current (FLA) as measured in the field — not necessarily the
nameplate FLA, which is measured at rated voltage. If the supply voltage is
consistently above or below nameplate, actual FLA will differ. Canadian
Electrical Code (CEC) and NEC allow 115–125% of nameplate FLA for standard
overload relay sizing, with the exact percentage depending on service factor and
motor type.
⚠️
Ambient temperature affects overload relay trip point
Bimetal overload relays are calibrated for a standard ambient temperature
(typically 20–40 °C depending on manufacturer). In high-ambient
locations such as rooftops in summer, the relay trips earlier than its marked
setting. In cold locations it trips later. Ambient-compensated relays correct
for this automatically. Always verify the relay type before adjusting trip
settings to resolve nuisance trips.
2.6.2 — Effects of Voltage Variations
NEMA standards permit ±10% of rated voltage. Most motors operate acceptably
within this range, but both high and low voltage cause problems — often different
problems than technicians expect. High voltage is not always “safe”, and low
voltage is frequently the cause of motor failures that appear as overloads.
💡
High Voltage — +10%
e.g. 264 V on a 240 V motor
Starting torque+21% ↑
Running torqueIncreases ↑
No-load currentIncreases ↑
Full-load currentSlightly less →
Speed (full load)Slight increase →
Iron core temperatureRises (saturation) ↑
Insulation stressHigher ↑
Power factorDecreases ↓
⚡
Low Voltage — −10%
e.g. 216 V on a 240 V motor
Starting torque−19% ↓
Running torqueDecreases ↓
No-load currentDecreases ↓
Full-load current+10–15% ↑
Speed (full load)Decreases ↓
Winding temperatureRises substantially ↑
Starting abilityMay fail to start ↓
Power factorIncreases slightly ↑
🚫
Low voltage causes more failures than high voltage
Low voltage forces the motor to draw higher current to produce the same
shaft output. Higher current means higher I²R heating in the windings.
The relationship is approximately: a 10% voltage reduction causes a 15–20%
increase in full-load current and a 20–25% increase in winding temperature
rise. This accelerates insulation degradation and is the leading electrical
cause of premature motor failure. Always measure voltage at the motor terminals,
not at the panel — conductor voltage drop can be substantial.
2.6.3 — Torque Is Proportional to Voltage Squared
The relationship between supply voltage and available motor torque is not linear
— it is proportional to the square of the voltage. This
means small voltage deviations have a disproportionately large effect on starting
ability and breakdown torque.
T ∝ V²
Torque available at any given slip is proportional to the square of the applied voltage. A 10% voltage reduction reduces available torque by approximately 19%, not 10%.
100%Nominal Voltage
100% rated torque
Baseline
+10%High Voltage (110%)
121% rated torque
1.1² = 1.21 → +21%
−10%Low Voltage (90%)
81% rated torque
0.9² = 0.81 → −19%
The practical implication for HVAC/R technicians: a compressor motor with marginal
torque at rated voltage will fail to start reliably when the supply voltage drops
even slightly. A motor that starts fine in the morning (cooler, higher voltage)
may fail to restart after shutdown at mid-afternoon peak load (hotter, lower
voltage). This pattern — starts fine when cool, locks out on hot restart
— is a classic symptom of low voltage combined with a borderline starting device.
📊
Measure voltage during the starting attempt — not before
Supply voltage often sags significantly during motor starting due to the
high inrush current. A supply that reads 240 V at no load may drop to 210 V
during starting, reducing available starting torque by 24% compared to nominal.
Always use a true RMS voltmeter and observe the voltage during a timed start
sequence to capture voltage sag, not just the static voltage.
2.6.4 — Voltage Unbalance in Three-Phase Systems
In a three-phase system, if the three line voltages are not equal,
voltage unbalance exists. Even a small voltage unbalance causes
a disproportionately large current unbalance, because the negative-sequence
component of voltage drives a much larger current response than an equal
magnitude positive-sequence deviation.
% Voltage Unbalance = (Max deviation from average ÷ Average voltage) × 100
Example: Phase voltages of 240, 236, 248 V → Average = 241.3 V → Max deviation = 6.7 V → Unbalance = 2.8%
Voltage Unbalance vs. Current Imbalance — Why Small Is Dangerous
Balanced System — 0% Voltage Unbalance
L1
100%
L2
100%
L3
100%
3% Voltage Unbalance → ~27% Current Imbalance
L1
88%
L2
100%
L3
127%
The winding carrying the highest current overheats, even if the average
current appears normal. The NEMA de-rating rule for voltage unbalance is approximately:
1% voltage unbalance causes 6–10% current unbalance, and motor
efficiency and rated load capacity must be de-rated according to NEMA MG-1 tables.
At 5% voltage unbalance, a motor must be de-rated to about 75% of its nameplate
horsepower or it will operate at elevated temperatures.
⚠️
Sources of Voltage Unbalance in HVAC/R Systems
Single-phase loads (lighting, receptacles) unevenly distributed across the three phases of the panel — the most common cause in commercial buildings.
Faulty or open utility transformer winding — produces large unbalance and usually requires utility company involvement to resolve.
Loose or corroded connection at the motor terminals, starter contacts, or fused disconnect — creates resistance heating and unequal voltage drop.
Open delta transformer bank with unequal load on each leg — common on older commercial sites.
Single-phase fault to ground on one feeder conductor in a multi-wire circuit — presents as sudden, severe unbalance.
⚠️
Check all three voltages — not just one
Always measure L1–L2, L2–L3, and L1–L3 (or phase-to-neutral on all
three phases) when diagnosing a suspected overheating or overcurrent complaint on
a three-phase motor. A single voltage reading between two phases will not reveal
unbalance. Measure at the motor terminals, not at the panel, to capture any
conductor-level resistance differences.
2.6.5 — Practical Diagnosis — Load & Voltage Problems
Most motor problems in the field involve some combination of mechanical overload,
voltage supply issues, or both acting together. The following principles allow a
systematic approach to diagnosis using a clamp-on ammeter and a true RMS voltmeter.
Step-by-Step Diagnostic Procedure
Measure supply voltage at the motor terminals under load —
not at the panel, not at idle. Record all three phases (or L–N on single-phase).
Compare to motor nameplate rating. Voltages more than ±10% outside nameplate
indicate a supply problem that must be resolved before any other diagnosis.
Measure running current on all phases with a clamp-on ammeter
during steady-state operation. Compare to nameplate FLA. Current within 10% of
FLA is normal. Current significantly above FLA indicates overloading, low voltage,
or a motor fault.
Calculate voltage unbalance using the three measured phase voltages.
Maximum deviation from average divided by average, times 100. Values above 2%
require investigation and de-rating; values above 5% require shutdown and correction.
Check for conductor voltage drop by measuring voltage both at
the panel and at the motor terminals simultaneously. A large difference
(>3 V on a 240 V circuit) indicates undersized conductors, poor connections,
or excessive run length. Long wire runs in equipment rooms and rooftop installations
are a frequent cause of low voltage at the motor.
Verify the mechanical load is within the motor’s rated HP.
Check for fouled evaporator or condenser coils, restricted airflow, bearing
drag, seized components, or refrigerant overcharge causing high discharge
pressure on compressor motors.
Check winding temperature after sustained operation by placing
a temperature probe on the motor frame. Compare to the motor’s ambient plus
rated temperature rise. Insulation class limits (from 2.01): Class B = 130 °C,
Class F = 155 °C, Class H = 180 °C total (winding temp = ambient +
temperature rise).
Verify overload relay setpoint is set to actual measured FLA,
not just nameplate value. Account for ambient temperature correction if using
bimetal relays in high-ambient locations. Replace with ambient-compensated relays
where appropriate.
✅
Quick Reference — Current vs. Probable Cause
Measured Current
Voltage Normal?
Most Likely Cause
Well below FLA (<70%)
Yes
Motor lightly loaded; normal if at design condition (e.g., economiser mode)
At or near FLA
Yes
Normal operation at designed full load
Above FLA (110–125%)
Yes
Mechanical overload — check driven equipment
Above FLA (110–125%)
Low −10%
Low voltage forcing higher current — check supply and conductors
Significantly above FLA (>125%)
Yes
Severe overload, jammed load, or winding fault — trip and investigate
Unequal between phases
Unbalanced
Voltage unbalance — measure all three phases and trace source
Two phases high, one very low
One phase low/open
Single-phasing condition — motor running on two legs; shut down immediately
🚫
Single-phasing is a motor emergency — act immediately
If one phase of a three-phase supply is lost (open fuse, loose lug, or utility
fault), the motor attempts to continue running on two phases. Current in the
remaining two windings rises to 150–200% of normal. A motor that trips on
overload and resets repeatedly should be treated as a single-phasing suspect
until proven otherwise. Measure all three phases before assuming the overload
relay is simply undersized.