Unit 6 — Refrigeration System Components
Section 1 — Compressors

1.3 — Methods of Compressor Cooling

Compressors generate significant heat from compression work, motor losses, and friction. This heat must be removed to prevent overheating, oil breakdown, and motor winding damage. This lesson covers the five cooling methods used across different compressor types and applications: suction gas, air, water, liquid injection, and oil cooling.

Suction Gas Air Cooling Water Cooling Liquid Injection Oil Cooling 313A / 313D

Jump to

1.3.1 — Superheat & Subcooling

Superheat and subcooling describe the thermal state of the refrigerant at two critical points in the vapour-compression cycle. Both are measured in degrees of temperature difference from the saturation point at the prevailing pressure, and both are essential diagnostic and commissioning parameters for every refrigeration technician.

Superheat

Superheat is the temperature increase of refrigerant vapour above its saturation temperature at a given pressure. If the saturation temperature at suction pressure is 5°C (41°F) and the actual suction line temperature is 15°C (59°F), the suction superheat is 10°C (18°F).

🌡️

Suction Superheat

Measured at the compressor suction port (or at the outlet of the evaporator). The recommended range for most applications is 10–20°F (5.5–11°C). Adequate suction superheat confirms that all liquid has evaporated before reaching the compressor, protecting against liquid slugging. Excessive superheat indicates a starved evaporator or refrigerant undercharge.

🌡️

Discharge Superheat

The superheat of the refrigerant vapour leaving the compressor discharge port. A useful indicator of compressor health: if discharge superheat is very low, liquid may be reaching the compressor; if it is excessively high, the suction gas is too hot when it enters (often due to high suction superheat or high compression ratio), stressing the compressor oil and valves.

Low Suction Superheat — Risk

Suction superheat below 5°F (2.8°C) means liquid refrigerant may be present in the suction line. Even small amounts of liquid entering the compressor at high velocity cause valve damage (hydraulic shock) and wash the oil film from cylinder walls, leading to accelerated wear. Correct immediately by adjusting the metering device or addressing the cause of liquid floodback.

Subcooling

Subcooling is the temperature reduction of liquid refrigerant below its saturation temperature at a given pressure. If the saturation temperature at liquid line (condensing) pressure is 40°C (104°F) and the actual liquid line temperature is 35°C (95°F), the subcooling is 5°C (9°F).

💡

Why Subcooling Is Important

  • Prevents flash gas at the metering device: if subcooling is insufficient, the pressure drop along the liquid line reduces the pressure below the saturation point, and some liquid flashes to vapour before it reaches the metering device — this reduces system capacity and can cause erratic metering device operation
  • Indicates adequate refrigerant charge: subcooling is one of the primary indicators used during charging; a system with correct subcooling (typically 10–20°F / 5.5–11°C for most systems) is presumed to have adequate refrigerant in the condenser
  • Increases refrigeration effect: subcooled liquid enters the evaporator with more heat absorption capacity because it must first warm to saturation temperature before evaporating; this marginally improves system COP
  • Excessive subcooling can indicate refrigerant overcharge, a restriction in the liquid line, or a liquid-line heat exchanger in the system; verify by checking system pressures and design specifications

1.3.2 — Discharge Temperature

The discharge temperature is the temperature of the refrigerant gas leaving the compressor at the discharge port. It is one of the most useful indicators of overall system and compressor health and is routinely measured during commissioning, service calls, and performance verification.

🔥

Maximum Safe Discharge Temperature

Most manufacturers specify a maximum continuous discharge temperature of 107°C (225°F). Above this threshold, refrigeration oil begins to break down, carbonizes on valve plates and discharge passages, and loses its lubricating properties. Sustained high discharge temperatures are a primary cause of early compressor failure.

📈

What Raises Discharge Temperature

High compression ratio (high head pressure, low suction pressure); high suction superheat (overheated gas entering the compressor); low volumetric efficiency; and high ambient temperature around the compressor. Each of these factors adds heat to the gas during compression, raising the discharge temperature independently of the others.

🔍

Measuring Discharge Temperature

Measure with a thermocouple or electronic thermometer as close to the compressor discharge port as possible — ideally within 150 mm (6 in). The temperature drops rapidly along the discharge line as the gas gives up heat. A reading taken farther down the discharge line significantly underestimates the true compressor discharge temperature.

⚠️

Consequences of Excessive Discharge Temperature

  • Oil carbonization: oil deposits form as hard carbon particles on valve plates, discharge ports, and discharge mufflers; particles circulate in the system and can restrict small-bore components
  • Acid formation: at high temperatures, oil and refrigerant react to form acids that attack copper plating, motor windings, and bearing surfaces
  • Valve plate damage: carbon deposits on valve seats prevent valves from sealing fully, reducing volumetric efficiency and raising discharge temperature further — a self-reinforcing failure cycle
  • Reduced oil viscosity: oil thins at high temperature, reducing film strength at bearing surfaces; bearing wear accelerates
  • Always investigate and correct the root cause of high discharge temperature — do not simply monitor it and hope it resolves

1.3.3 — Suction Gas Cooling

Most hermetic and semi-hermetic compressors use returning suction gas to cool the motor and compressor. Cool, low-pressure vapour from the evaporator passes over the motor windings before entering the compression chamber. This method is simple and requires no external cooling system, but depends on adequate suction superheat to prevent liquid refrigerant from reaching motor windings.

🌡️

Design Considerations

  • Motor heat load raises suction gas temperature before it enters the compression chamber, contributing to higher discharge temperature
  • Excessive suction superheat reduces refrigerant vapour density, lowering mass flow rate and capacity
  • Low suction pressure applications (low-temperature refrigeration) provide less cooling because lower vapour density carries less heat per unit volume
  • Some designs route suction gas directly to the cylinders, bypassing the motor, when lower discharge temperatures are required
🔧
Field Practice

Maintain suction superheat within the manufacturer’s specified range — typically 10–20°F (5.5–11°C) — to ensure adequate motor cooling while preventing liquid refrigerant damage. Monitor suction and discharge temperatures to verify proper operation. Inadequate refrigerant charge or a malfunctioning metering device are the most common causes of suction gas cooling problems.

1.3.4 — Air Cooling

Open-drive compressors and some semi-hermetic designs use ambient air for cooling. Fans blow air over the compressor exterior, removing heat from cylinder heads, motor housing, and crankcase. This is the simplest external cooling method and requires no water supply or piping.

💨

Design Considerations

  • Requires adequate clear space around the compressor for unrestricted airflow; recirculation of hot discharge air raises ambient temperature and reduces cooling effectiveness
  • Effectiveness is limited by ambient temperature — in high-ambient environments, air cooling alone may be insufficient to maintain safe discharge temperatures
  • Cooling fins cast into cylinder heads increase surface area; fins must be kept clean to maintain heat transfer
  • Some installations use a fan and shroud to direct airflow across specific heat-generating surfaces
🔧
Field Practice

Ensure adequate clearance around the compressor for airflow per manufacturer specifications. Keep cooling fins clean and free of debris, oil film, and dust accumulation. Verify that cooling fans operate at rated speed. In compressor rooms, confirm ventilation is sufficient to prevent heat build-up — ambient temperature at the compressor should not exceed the design maximum.

1.3.5 — Water Cooling

Larger compressors often use water-cooled heads, oil coolers, or jacketed cylinders to remove heat. Water cooling is more effective than air cooling per unit of surface area and allows reliable operation at high ambient temperatures where air cooling would be marginal.

💧

Water-Cooled Heads

Water passages cast into cylinder heads remove heat of compression directly at the source. This reduces discharge temperature, lowers oil temperature at the discharge valves, and improves compressor efficiency. Water flow is regulated to maintain proper head temperature — overcooling can cause refrigerant condensation in the discharge passages.

🚬

Water-Cooled Oil Coolers

Shell-and-tube or plate heat exchangers cool lubricating oil before it returns to the compressor bearings. Water temperature must be controlled carefully — overcooling the oil below its viscosity optimum reduces bearing film strength, while undercooling allows oil to thin and lose lubrication effectiveness.

🔧
Field Practice

Maintain water flow rates and supply temperatures per manufacturer specifications — typically 85–95°F (29–35°C) supply water. Inspect and clean water-side surfaces regularly to prevent fouling and scale buildup, which sharply reduce heat transfer. Use treated water or a closed-loop system to prevent corrosion and biological growth. Protect against freezing if the system is exposed to ambient temperatures below 0°C (32°F).

1.3.6 — Liquid Injection Cooling

Some screw compressors inject liquid refrigerant directly into the compression chamber to absorb heat of compression. This reduces discharge temperature and allows operation at higher compression ratios than would otherwise cause excessive temperatures.

💦

Design Considerations

  • Liquid injection point is located partway through the compression process, where partial compression has already raised refrigerant temperature
  • Injection rate is modulated based on measured discharge temperature to maintain temperature within safe limits
  • Cooling the partially compressed vapour reduces the work done in the remaining compression, slightly reducing efficiency — the tradeoff for enabling high-compression-ratio operation
  • Enables operation at conditions (high ambient, low suction temperature) that would otherwise produce discharge temperatures beyond safe limits for oil and valves

Economizer Cooling — A More Efficient Alternative

Some systems use an economizer port at an intermediate pressure point in the compressor. Partially expanded refrigerant from the condenser — rather than fully liquid refrigerant — provides cooling at the intermediate pressure stage. This approach is more efficient than simple liquid injection because it also increases system capacity: the additional refrigerant injected at the economizer port contributes to the final compressed output.

1.3.7 — Oil Cooling

In oil-flooded screw compressors, the large volume of injected oil absorbs compression heat directly. This hot oil must be cooled before reinjection into the compression chamber. Four oil cooling methods are used, selected based on available utilities, ambient conditions, and installation requirements.

💨

Air-Cooled Oil Cooler

Finned coils with fans reject oil heat to ambient air. Simple, requiring no water supply or additional utilities. Effectiveness is limited by ambient temperature — in high-ambient conditions, air cooling may not maintain oil temperature within the required range.

💧

Water-Cooled Oil Cooler

Shell-and-tube heat exchangers cool oil using condenser water or a dedicated water circuit. More effective than air cooling and maintains consistent oil temperature regardless of ambient conditions. Common in larger industrial and commercial screw compressor installations.

🔥

Thermosyphon Oil Cooler

Uses the evaporation of liquid refrigerant drawn from the condenser to cool the oil. Hot oil warms the refrigerant, which evaporates and returns to the condenser. Self-regulating — cooling capacity automatically matches heat load. No pump or external utilities required beyond the refrigerant circuit.

💦

Liquid-Injection Oil Cooler

Cool liquid refrigerant is mixed directly with hot oil before reinjection into the compressor. Simple and compact. Because some of the refrigerant evaporates into the oil stream, this method affects oil-refrigerant ratio and requires careful control to avoid refrigerant dilution of the oil charge.

🔧
Field Practice

Monitor oil temperature continuously — typical operating range is 130–180°F (54–82°C). Maintain proper cooling medium flow and supply temperature. Clean oil coolers on a scheduled basis; fouled surfaces reduce heat transfer and allow oil temperature to climb toward unsafe levels. Verify that temperature control valves cycle correctly. If oil temperature cannot be controlled within range, investigate cooling circuit flow, fouling, and ambient conditions before concluding the oil cooler must be replaced.

Test Your Knowledge
↑ Top