Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 6 — Introduction to System Maintenance

6.3 — Electrical Efficiency Issues

Electrical faults waste energy, accelerate component wear, and create safety hazards. This lesson covers the electrical components most often responsible for efficiency loss in 313A/313D Level 1 systems, and the additional service requirements — water treatment, coil cleaning, condensate management, and filter maintenance — that keep equipment running at rated performance.

Jump to

6.3.1 — Capacitors & Potential Relays

Run capacitors maintain the phase shift needed for single-phase motor operation. A weak capacitor causes the motor to draw higher current, run hotter, and lose torque. Start capacitors provide a brief boost for high-inertia loads (compressors, large fans); a potential relay drops the start capacitor out of circuit once the motor reaches approximately 75 % of running speed.

Testing Capacitors

Measure capacitance with a capacitor-function multimeter or dedicated capacitor tester. Discharge the capacitor first by briefly shorting its terminals through a 20 kΩ resistor — never short them directly as the current spike can damage the meter.

Capacitor Type Typical Range Tolerance Failure Symptom
Run (motor) 3–80 µF ±6 % Motor runs hot; high amps; hums but won’t start
Start (motor) 88–400 µF ±20 % Motor won’t start under load; trips overload
Dual-run (compressor + fan) Dual label (e.g. 40/5 µF) ±6 % Either or both motors affected; verify each section
Safety rule: Always discharge capacitors before handling, even if the unit has been off for several minutes. A 400 V capacitor can deliver a lethal shock minutes after power is removed.

Potential Relays

A potential relay coil opens its normally-closed contact when counter-EMF from the motor reaches the relay’s “pick-up” voltage. If the relay contact fails to open, the start capacitor remains in the circuit and overheats, eventually failing open or short. If the relay coil is open, the start capacitor never engages and the motor won’t start under load. Test the relay coil resistance (typically 8,000–20,000 Ω) and verify contact continuity (NC contact should read zero ohms at rest).

Worked Example — Weak Run Capacitor

A condenser fan motor is running but drawing 4.2 A on a unit with a 3.1 A nameplate FLA. The run capacitor is labelled 7.5 µF ± 6 %. Measured value: 5.8 µF.

Tolerance limit: 7.5 × 0.94 = 7.05 µF minimum. Measured 5.8 µF is 23 % low — well outside tolerance. The capacitor is replaced. After replacement, amp draw returns to 3.0 A and the motor runs noticeably cooler. Operating with a weak capacitor for an extended period would have degraded the motor windings and shortened motor life.

6.3.2 — Control Components: Contactors, Relays & Solenoid Coils

Contactors

The compressor contactor is a high-current switching device controlled by the 24 V thermostat circuit. Contactor problems that reduce efficiency:

Measure voltage drop across closed contacts; more than 0.2 V drop on a 24 V control circuit or more than 2 V on a 240 V power circuit indicates excessive resistance.

Relays

Control relays switch lower-current loads (fans, solenoids, defrost heaters). The same inspection and testing principles apply as for contactors. Additionally, check that relay mounting is secure — vibration loosens relay bases and causes intermittent contact problems that are difficult to reproduce during service visits.

Solenoid Coils

Solenoid valves control liquid line, hot gas, and reversing valve functions. A solenoid coil that draws excessive current runs hot and fails prematurely; a coil with an open winding prevents the valve from operating at all.

  1. Measure coil resistance with power off. Compare to manufacturer specification.
  2. Apply rated voltage; verify the valve actuates (audible “click” or feel shaft movement).
  3. Measure operating amperage; should match nameplate within 10 %.
  4. Feel the coil body after 5 minutes of operation; it should be warm but not too hot to hold.

6.3.3 — Motors, Overloads & Phase Imbalance

Motor Operating Efficiency

Electric motors in HVAC systems include compressor motors, condenser fan motors, evaporator fan motors, and pump motors. Motor efficiency deteriorates through:

Overload Protectors

Internal thermal overloads protect motor windings from sustained overcurrent. An overload that trips repeatedly indicates an underlying problem — never bypass or defeat an overload to restore operation. Instead, investigate:

Voltage Imbalance (Three-Phase Systems)

Voltage imbalance in a three-phase supply causes unequal current in each winding, creating a hot winding and reducing motor efficiency and life. NEMA MG-1 limits imbalance to 1 %; a 3.5 % imbalance increases temperature rise by approximately 25 %.

Voltage Imbalance Calculation

% Imbalance = (Max deviation from average ÷ Average voltage) × 100

Example: Phase voltages 208, 210, 218 V.
Average = (208 + 210 + 218) / 3 = 212 V.
Max deviation = |218 − 212| = 6 V.
% Imbalance = 6 / 212 × 100 = 2.8 % — investigate supply at the panel.

Wiring Inspection

Loose or corroded wire connections are a leading cause of electrical efficiency loss and fire hazard. High-resistance connections under load cause voltage drop and localised heating. During any service visit, check:

6.3.4 — Supply Voltage Conditions

Both high and low supply voltage reduce system efficiency and equipment life. Most HVAC equipment is designed to operate within ±10 % of nameplate voltage.

Condition Effect on Motor Effect on Compressor Corrective Action
Low voltage (<90 % nameplate) High current; overheating; reduced torque; fails to start under load Locked-rotor condition; trips overload; may not start Check panel voltage; inspect wire gauge and length; check disconnect contacts
High voltage (>110 % nameplate) Reduced current draw but increased insulation stress; shortened life Higher discharge pressure and temperatures; increased wear Verify utility supply voltage; report to building electrical maintenance
Voltage imbalance (>2 %) One winding overheats; vibration; efficiency loss Compressor overheats; reduced COP Measure all three phases; balance loads at panel; report persistent issues
Measurement timing: Always measure supply voltage under load (compressor running), not at no-load. Voltage sags under load reveal resistive connections and undersized conductors that are invisible at rest.

6.3.5 — Additional Service Requirements

Beyond electrical and mechanical diagnostics, scheduled maintenance includes several service requirements that directly sustain system efficiency and indoor air quality.

Water & Chemical Treatment (Cooling Towers / Evaporative Condensers)

Open evaporative systems concentrate dissolved minerals as water evaporates. Without treatment, scale deposits insulate heat-transfer surfaces (even 1/32 in. of calcium scale reduces heat transfer efficiency by ~8 %), and biological growth (Legionella bacteria) presents a serious health risk.

Coil Cleaning

Coil cleaning frequency depends on environment: commercial kitchen exhaust near condensers may require monthly cleaning; typical office buildings annually. Use the appropriate cleaner for the coil material:

Coil Material Approved Cleaner Type Notes
Aluminium fins / copper tubes Non-acid foaming coil cleaner (neutral or alkaline pH) Acid cleaners pit aluminium; rinse thoroughly
Copper fins / copper tubes Mild alkaline cleaner Avoid high-pressure water which bends fins
Stainless or epoxy-coated coils Manufacturer-specified cleaner only Verify compatibility before applying any chemical

Condensate Traps

Systems with negative-pressure drain pans (blow-through AHUs) require a condensate trap to prevent air from being drawn backward through the drain line, which would bypass the drain pan and spray condensate into the airstream. A properly sized trap must have a water seal height greater than the static pressure at the drain pan (in inches of water column).

Trap sizing rule: Seal height (in. w.c.) ≥ negative static pressure at drain pan + 1 in. for safety. Inspect and clean condensate traps at each maintenance visit; a dry trap in a blow-through unit will allow air ingress and drain pan overflow simultaneously.

Corrosion Testing

Coastal, industrial, and agricultural environments expose equipment to corrosive atmospheres (salt spray, ammonia, hydrogen sulphide). Testing methods:

Filter Changes

Air filters are the first line of defence for all downstream components. A loaded filter increases static pressure across the air handler, reduces airflow, and causes all the downstream problems discussed in Section 6.2.

Filter Type MERV Rating Typical Change Interval Notes
Fibreglass panel 1–4 Monthly Low efficiency; protects equipment only
Pleated polyester 7–13 Every 3 months Most common commercial type; balance between efficiency and pressure drop
High-efficiency (HEPA / bag) 14–16 Every 6–12 months Verify unit is rated for high static; measure pressure drop to confirm loading

Measure static pressure drop across the filter bank at every visit. Compare to the clean filter pressure drop from the manufacturer’s data. A filter loaded to 2× the clean drop is ready to change regardless of visual appearance — dark-coloured filters can be loaded with fine particles not visible to the eye.

Worked Example — Filter Pressure Drop & Airflow

An AHU fan is rated to deliver 2,400 CFM at 0.5 in. w.c. external static pressure. The duct system consumes 0.35 in. w.c. Clean filter pressure drop: 0.08 in. w.c. The technician measures filter pressure drop at 0.22 in. w.c. on this visit.

Available static for the fan’s external resistance: 0.35 (duct) + 0.22 (filter) = 0.57 in. w.c.
This exceeds the fan rating of 0.50 in. w.c., so airflow has already dropped below 2,400 CFM. The filter must be changed to restore design airflow and prevent evaporator coil icing.

Test Your Knowledge
↑ Top