Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 6 — Introduction to System Maintenance
6.3 — Electrical Efficiency Issues
Electrical faults waste energy, accelerate component wear, and create safety hazards.
This lesson covers the electrical components most often responsible for efficiency loss
in 313A/313D Level 1 systems, and the additional service requirements —
water treatment, coil cleaning, condensate management, and filter maintenance —
that keep equipment running at rated performance.
Jump to
6.3.1 — Capacitors & Potential Relays
Run capacitors maintain the phase shift needed for single-phase motor operation.
A weak capacitor causes the motor to draw higher current, run hotter, and lose torque.
Start capacitors provide a brief boost for high-inertia loads (compressors, large fans);
a potential relay drops the start capacitor out of circuit once the motor reaches
approximately 75 % of running speed.
Testing Capacitors
Measure capacitance with a capacitor-function multimeter or dedicated capacitor tester.
Discharge the capacitor first by briefly shorting its terminals through a 20 kΩ
resistor — never short them directly as the current spike can damage the meter.
Capacitor Type
Typical Range
Tolerance
Failure Symptom
Run (motor)
3–80 µF
±6 %
Motor runs hot; high amps; hums but won’t start
Start (motor)
88–400 µF
±20 %
Motor won’t start under load; trips overload
Dual-run (compressor + fan)
Dual label (e.g. 40/5 µF)
±6 %
Either or both motors affected; verify each section
Safety rule: Always discharge capacitors before handling, even if the
unit has been off for several minutes. A 400 V capacitor can deliver a lethal shock
minutes after power is removed.
Potential Relays
A potential relay coil opens its normally-closed contact when counter-EMF from the
motor reaches the relay’s “pick-up” voltage. If the relay contact
fails to open, the start capacitor remains in the circuit and overheats, eventually
failing open or short. If the relay coil is open, the start capacitor never engages
and the motor won’t start under load. Test the relay coil resistance (typically
8,000–20,000 Ω) and verify contact continuity (NC contact should read zero
ohms at rest).
Worked Example — Weak Run Capacitor
A condenser fan motor is running but drawing 4.2 A on a unit with a 3.1 A nameplate
FLA. The run capacitor is labelled 7.5 µF ± 6 %. Measured value: 5.8 µF.
Tolerance limit: 7.5 × 0.94 = 7.05 µF minimum. Measured 5.8 µF is 23 % low —
well outside tolerance. The capacitor is replaced. After replacement, amp draw returns
to 3.0 A and the motor runs noticeably cooler. Operating with a weak capacitor for an
extended period would have degraded the motor windings and shortened motor life.
6.3.2 — Control Components: Contactors, Relays & Solenoid Coils
Contactors
The compressor contactor is a high-current switching device controlled by the 24 V
thermostat circuit. Contactor problems that reduce efficiency:
Pitted or burned contacts: Increased contact resistance raises heat and voltage drop; motor receives reduced voltage. Inspect contacts visually; replace if pitting depth exceeds 1/32 in. or if contacts are welded.
Weak hold-in coil: Contacts chatter under load, causing arcing and further pitting. Check coil voltage and resistance.
Welded contacts: Compressor runs continuously regardless of thermostat; replace immediately.
Measure voltage drop across closed contacts; more than 0.2 V drop on a 24 V control circuit
or more than 2 V on a 240 V power circuit indicates excessive resistance.
Relays
Control relays switch lower-current loads (fans, solenoids, defrost heaters). The same
inspection and testing principles apply as for contactors. Additionally, check that relay
mounting is secure — vibration loosens relay bases and causes intermittent contact
problems that are difficult to reproduce during service visits.
Solenoid Coils
Solenoid valves control liquid line, hot gas, and reversing valve functions. A solenoid
coil that draws excessive current runs hot and fails prematurely; a coil with an open
winding prevents the valve from operating at all.
Measure coil resistance with power off. Compare to manufacturer specification.
Apply rated voltage; verify the valve actuates (audible “click” or feel shaft movement).
Measure operating amperage; should match nameplate within 10 %.
Feel the coil body after 5 minutes of operation; it should be warm but not too hot to hold.
6.3.3 — Motors, Overloads & Phase Imbalance
Motor Operating Efficiency
Electric motors in HVAC systems include compressor motors, condenser fan motors, evaporator
fan motors, and pump motors. Motor efficiency deteriorates through:
Winding degradation: Heat cycles and moisture degrade insulation; measure winding resistance and megohm insulation resistance annually on critical motors.
Bearing wear: Increased friction raises motor temperature and amp draw. Listen for grinding, rumbling, or squealing; replace bearings before failure causes winding damage.
Contaminated windings: Grease or dust on motor windings reduces heat dissipation. Clean with approved electrical contact cleaner.
Overload Protectors
Internal thermal overloads protect motor windings from sustained overcurrent.
An overload that trips repeatedly indicates an underlying problem — never
bypass or defeat an overload to restore operation. Instead, investigate:
Measure motor amp draw against nameplate RLA/FLA — over 10 % above FLA warrants investigation
Check for supply voltage within ±10 % of nameplate
Verify capacitor condition (single-phase motors)
Check for mechanical binding — fan blades, bearings, compressor seizure
Confirm airflow is adequate — an obstructed motor casing overheats
Voltage Imbalance (Three-Phase Systems)
Voltage imbalance in a three-phase supply causes unequal current in each winding,
creating a hot winding and reducing motor efficiency and life. NEMA MG-1 limits
imbalance to 1 %; a 3.5 % imbalance increases temperature rise by approximately 25 %.
Voltage Imbalance Calculation
% Imbalance = (Max deviation from average ÷ Average voltage) × 100
Example: Phase voltages 208, 210, 218 V.
Average = (208 + 210 + 218) / 3 = 212 V.
Max deviation = |218 − 212| = 6 V.
% Imbalance = 6 / 212 × 100 = 2.8 % — investigate supply at the panel.
Wiring Inspection
Loose or corroded wire connections are a leading cause of electrical efficiency loss and
fire hazard. High-resistance connections under load cause voltage drop and localised
heating. During any service visit, check:
All terminal screws in the disconnect, contactor, control board, and motor terminal box are tight
No signs of overheating (discoloration, melted insulation, carbon tracks)
Wire gauge matches the circuit breaker rating and equipment nameplate
Wiring is secured away from hot surfaces, moving parts, and sharp edges
6.3.4 — Supply Voltage Conditions
Both high and low supply voltage reduce system efficiency and equipment life. Most HVAC
equipment is designed to operate within ±10 % of nameplate voltage.
Condition
Effect on Motor
Effect on Compressor
Corrective Action
Low voltage (<90 % nameplate)
High current; overheating; reduced torque; fails to start under load
Locked-rotor condition; trips overload; may not start
Reduced current draw but increased insulation stress; shortened life
Higher discharge pressure and temperatures; increased wear
Verify utility supply voltage; report to building electrical maintenance
Voltage imbalance (>2 %)
One winding overheats; vibration; efficiency loss
Compressor overheats; reduced COP
Measure all three phases; balance loads at panel; report persistent issues
Measurement timing: Always measure supply voltage under load (compressor
running), not at no-load. Voltage sags under load reveal resistive connections and
undersized conductors that are invisible at rest.
6.3.5 — Additional Service Requirements
Beyond electrical and mechanical diagnostics, scheduled maintenance includes several
service requirements that directly sustain system efficiency and indoor air quality.
Water & Chemical Treatment (Cooling Towers / Evaporative Condensers)
Open evaporative systems concentrate dissolved minerals as water evaporates.
Without treatment, scale deposits insulate heat-transfer surfaces (even 1/32 in.
of calcium scale reduces heat transfer efficiency by ~8 %), and biological growth
(Legionella bacteria) presents a serious health risk.
Measure conductivity (total dissolved solids) and compare to target cycles of concentration
Bleed-down the sump to control mineral concentration when conductivity exceeds set point
Add biocide on schedule; verify residual with test strips
Inspect drift eliminators and distribution nozzles for blockage
Record all water treatment activities in a log book
Coil Cleaning
Coil cleaning frequency depends on environment: commercial kitchen exhaust near
condensers may require monthly cleaning; typical office buildings annually.
Use the appropriate cleaner for the coil material:
Coil Material
Approved Cleaner Type
Notes
Aluminium fins / copper tubes
Non-acid foaming coil cleaner (neutral or alkaline pH)
Acid cleaners pit aluminium; rinse thoroughly
Copper fins / copper tubes
Mild alkaline cleaner
Avoid high-pressure water which bends fins
Stainless or epoxy-coated coils
Manufacturer-specified cleaner only
Verify compatibility before applying any chemical
Condensate Traps
Systems with negative-pressure drain pans (blow-through AHUs) require a condensate
trap to prevent air from being drawn backward through the drain line, which would
bypass the drain pan and spray condensate into the airstream. A properly sized trap
must have a water seal height greater than the static pressure at the drain pan
(in inches of water column).
Trap sizing rule: Seal height (in. w.c.) ≥ negative static pressure
at drain pan + 1 in. for safety. Inspect and clean condensate traps at each
maintenance visit; a dry trap in a blow-through unit will allow air ingress and
drain pan overflow simultaneously.
Corrosion Testing
Coastal, industrial, and agricultural environments expose equipment to corrosive
atmospheres (salt spray, ammonia, hydrogen sulphide). Testing methods:
Visual inspection: Look for white or green oxidation on aluminium fins, green patina on copper, rust on steel cabinets
Copper corrosion coupons: Standardised coupons placed in the airstream; measured mass loss quantifies corrosion rate
Electronic corrosion monitor: Provides real-time data for critical applications
Where corrosion is confirmed, consider coil coatings (phenolic, epoxy) and more frequent coil cleaning
Filter Changes
Air filters are the first line of defence for all downstream components. A loaded filter
increases static pressure across the air handler, reduces airflow, and causes all the
downstream problems discussed in Section 6.2.
Filter Type
MERV Rating
Typical Change Interval
Notes
Fibreglass panel
1–4
Monthly
Low efficiency; protects equipment only
Pleated polyester
7–13
Every 3 months
Most common commercial type; balance between efficiency and pressure drop
High-efficiency (HEPA / bag)
14–16
Every 6–12 months
Verify unit is rated for high static; measure pressure drop to confirm loading
Measure static pressure drop across the filter bank at every visit. Compare to the
clean filter pressure drop from the manufacturer’s data. A filter loaded to
2× the clean drop is ready to change regardless of visual appearance —
dark-coloured filters can be loaded with fine particles not visible to the eye.
Worked Example — Filter Pressure Drop & Airflow
An AHU fan is rated to deliver 2,400 CFM at 0.5 in. w.c. external static pressure.
The duct system consumes 0.35 in. w.c. Clean filter pressure drop: 0.08 in. w.c.
The technician measures filter pressure drop at 0.22 in. w.c. on this visit.
Available static for the fan’s external resistance: 0.35 (duct) + 0.22 (filter) = 0.57 in. w.c.
This exceeds the fan rating of 0.50 in. w.c., so airflow has already dropped below 2,400 CFM.
The filter must be changed to restore design airflow and prevent evaporator coil icing.