Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 6 — Introduction to System Maintenance

6.4 — Defects: Causes & Repairs

Identifying a defect is only half the job — a technician must also understand why it occurred and carry out the correct repair procedure. This lesson links specific component failures to their root causes and the standard repair sequences recognised in 313A/313D Level 1 practice.

Jump to

6.4.1 — Bearings, Belts & Pulleys

Bearing Failures

Bearings support rotating shafts in motors, compressors, and fan assemblies. Premature bearing failure is caused by:

Diagnosis: listen for grinding, rumbling, or squealing. A stethoscope or vibration pen placed on the bearing housing amplifies the sound. Measure motor amperage — a worn bearing increases friction and amp draw before failure. Replace bearings in matched pairs (both ends of the shaft) to prevent an imbalanced shaft load on the new bearing.

V-Belt Defects & Tensioning

V-belts transmit power from motors to fan sheaves on belt-drive AHUs. A worn or improperly tensioned belt slips under load, generates heat, reduces airflow, and wears the sheave groove prematurely.

Defect Symptom Cause Repair
Belt slipping Squealing; reduced fan speed; belt glazed on sides Undertension; worn sheave; oil contamination Adjust tension; replace belt; clean or replace sheave
Belt cracking Visible cracks on inner surface; belt pieces in housing Age hardening; ozone; heat; misalignment Replace belt; check alignment
Belt fraying Fibres visible on belt edges Sheave groove worn sharp; belt rubbing guard Replace sheave; adjust belt guard clearance
Overtensioned belt Excessive bearing load; premature bearing and belt failure Tension set too high; belt not re-checked after run-in Adjust to manufacturer deflection specification

Belt Tension Check Procedure

The deflection method: apply a perpendicular force at the midpoint of the belt span equal to the manufacturer’s recommended force (typically listed in the O&M manual or on a belt tension chart). Measure deflection; compare to the target (typically 1/64 in. per inch of belt span, e.g. 24 in. span = 3/8 in. deflection). Re-tension if outside the ±1/16 in. tolerance. Always re-check tension after the first 24 hours of operation as new belts seat into the sheave groove and loosen slightly.

Pulley (Sheave) Wear & Alignment

A worn sheave groove becomes rounded (hourglass profile), reducing the belt’s wedging action and causing slip even at correct tension. Check groove profile with a sheave gauge or straightedge. Misaligned sheaves cause the belt to ride up on one side, generating heat and uneven wear. Use a straightedge across both sheave faces to check parallel and angular alignment simultaneously; maximum misalignment should not exceed 1/16 in. per foot of shaft centre distance.

6.4.2 — Filter Driers & Incorrect Charge Repair

Dirty or Plugged Filter Driers

The filter drier protects the system from moisture and debris. A saturated or plugged drier creates a pressure drop in the liquid line that promotes flash gas upstream of the metering device, reducing capacity. Diagnosis: feel the inlet and outlet of the drier — a significant temperature difference (more than 2–3 °F) indicates a restriction. On some units, frost or condensation forms on the outlet side of a plugged drier as the pressure drops enough to approach saturation temperature.

Always replace the filter drier when opening the refrigerant circuit for any repair. A drier that has been exposed to atmospheric air has absorbed moisture and is partially saturated before re-installation.

Replacement procedure:

  1. Recover refrigerant per local regulations.
  2. Cut or unsweat the old drier; note the direction of flow arrow on the shell.
  3. Install the new drier with the flow arrow in the correct direction (liquid enters the inlet end).
  4. Braze or flare connections; purge with dry nitrogen during brazing to prevent copper oxide scale.
  5. Pressure-test, evacuate to ≤300 microns, verify vacuum hold, then recharge.

Incorrect Charge Repair Procedure

Adding refrigerant to a leaking system without finding and fixing the leak is not a repair — it is a temporary measure that violates refrigerant management regulations. The correct procedure:

  1. Locate the leak: Use an electronic detector, UV dye (where already installed), or nitrogen pressure test. Document the leak location.
  2. Recover the remaining charge to an approved recovery cylinder. Weigh the recovery to determine how much refrigerant was lost.
  3. Repair the leak: Re-sweat the joint, replace the flare fitting, or replace the component as required.
  4. Replace the filter drier (the circuit has been open).
  5. Pressure-test with dry nitrogen to 1.1 × the maximum operating pressure. Hold for a minimum of 15 minutes with no drop.
  6. Evacuate to ≤300 microns; measure with an electronic micron gauge (not a compound gauge needle). Isolate the vacuum pump and hold for 15 minutes — pressure rise of more than 100 microns indicates moisture or a leak.
  7. Recharge to manufacturer’s subcooling or superheat specification. Record refrigerant type, amount added, and ambient conditions on the service record.

6.4.3 — Valve Defects & Operation

Leaking Compressor Valves

As discussed in 6.2, worn or broken compressor valves reduce volumetric efficiency. The repair for leaking compressor valves in a reciprocating compressor is a valve plate replacement, which requires opening the compressor head. In practice, a compressor with confirmed valve damage is often replaced rather than repaired in the field, particularly for hermetic and semi-hermetic units. Before condemning a compressor:

TXV (Thermostatic Expansion Valve) Operation & Faults

The TXV meters refrigerant to maintain a set suction superheat. TXV faults fall into two categories: hunting (unstable) and stuck (fixed).

Fault Symptom Cause Repair/Action
TXV hunting Suction pressure oscillates; superheat swings widely; system short-cycles Sensing bulb poorly clamped to suction line; bulb in wrong location; insulation missing Re-clamp bulb; ensure bulb is at 4 or 8 o’clock position; insulate bulb; verify external equaliser is connected to correct port
TXV stuck open Low suction superheat; liquid may reach compressor; high suction pressure Debris under valve seat; loss of power element charge Replace TXV; install new filter drier
TXV stuck closed Very high superheat; low suction pressure; high discharge temp; system starved Wax plugging valve orifice (wrong oil/refrigerant mix); ice blockage; loss of power element Check for moisture and acid; replace TXV and drier; purge and recharge with correct refrigerant type
TXV underfeeding Moderate-to-high superheat; capacity below design Valve set too cold (adjustment); undersized for load; pressure drop in liquid line causing flash gas Adjust superheat set point (CW = higher superheat; CCW = lower superheat); verify liquid line pressure drop; confirm correct valve model

Worked Example — TXV Hunting Diagnosis

Suction pressure on an R-410A system oscillates between 90 and 130 psig in a 45-second cycle, with corresponding swings in suction superheat from 3 °F to 25 °F. Head pressure is stable. Compressor cycles on the low-pressure switch during each low-pressure event.

Inspection: the sensing bulb is clamped at the 12 o’clock position on the suction line. At the top of the pipe, oil pooling can coat the bulb and slow its thermal response, or the bulb senses liquid pooled from a previous flooded condition. The bulb is re-positioned to the 4 o’clock position and insulated with foam tape. After a 20-minute test run the system stabilises at 120 psig suction and 10 °F superheat with no hunting.

Service Valve Operation

Schrader-type and ball-type service valves must seat properly to isolate the circuit during service. Common defects:

6.4.4 — Refrigerant Piping & Sight Glasses

Piping Defects & Repairs

Refrigerant piping failures are almost always traced to one of the following causes:

Sight Glass Interpretation & Defects

The sight glass in the liquid line provides a visual indication of refrigerant charge and moisture level. A properly charged system shows a clear, bubble-free window under steady-state operating conditions.

Observation Meaning Action
Clear glass, no bubbles Sufficient charge; liquid fully subcooled Verify with superheat/subcooling measurements before adding refrigerant
Bubbles or foam streaming through Flash gas in liquid line — undercharge or liquid line restriction or insufficient subcooling Measure subcooling; check liquid line temperature drop; rule out restriction before adding charge
Moisture indicator yellow/orange Moisture present in system Replace filter drier; operate system; re-check indicator after 24 hours
Moisture indicator green Dry condition confirmed No action required for moisture
Oil streaks or dark fluid visible Oil carryover; possible system contamination Sample refrigerant and oil for acid and moisture; check compressor
Key point: A clear sight glass does not confirm a correct charge — it only confirms there is no flash gas at that location. An overcharged system also shows a clear glass. Always use subcooling and superheat measurements to set final charge.

6.4.5 — Insufficient Capacity & Fouled Heat Exchangers

Diagnosing Insufficient System Capacity

“Not cooling (or heating) enough” is the most common complaint in HVAC service. A structured diagnostic approach prevents misdiagnosis and unnecessary parts replacement:

  1. Confirm the complaint: Measure return and supply air temperatures. Calculated sensible cooling = CFM × 1.08 × ΔT. Compare to the rated tonnage (12,000 BTU/h per ton).
  2. Check airflow: Measure supply air velocity with an anemometer; confirm CFM matches system design (typically 400 CFM/ton for cooling).
  3. Measure coil pressures and temperatures: Suction, discharge, superheat, subcooling. Identify which, if any, are out of range.
  4. Check for load issues: Has building use changed? Are there new heat sources (IT equipment, additional occupants, glass exposure)? Is the thermostat calibrated?
  5. Compare to design conditions: Systems are rated at ARI/AHRI conditions (95 °F outdoor / 80 °F, 67 °F WB indoor). A system running in 105 °F ambient will produce less capacity than its nameplate rating — this is normal, not a defect.

Fouled Heat Exchangers

A fouled heat exchanger surface reduces both sensible and latent capacity. Even a thin biofilm on the evaporator fin surface reduces heat transfer coefficient by 20–30 %.

Heat Exchanger Fouling Type Primary Effect Cleaning Method
Evaporator coil Dust, biological growth, mould Reduced airflow; elevated suction superheat; restricted latent capacity Foaming coil cleaner; rinse in place or remove coil; treat with biocide
Condenser coil Dust, insects, cottonwood seeds, grease (kitchens) Elevated condensing temperature; high head pressure; increased kW Low-pressure water wash (outside-in direction); degreaser for grease fouling
Plate heat exchanger (chiller) Scale, biological growth, corrosion Increased approach temperature; reduced chiller COP Chemical cleaning (acid descale) per manufacturer; record before/after temperatures

Worked Example — Fouled Evaporator & Capacity Recovery

A retail walk-in cooler (R-404A) is maintaining 42 °F instead of the design 35 °F. Suction pressure is 22 psig (sat. temp. ≈17 °F); superheat 28 °F (very high). The evaporator coil is coated in a thick layer of grey dust and debris.

After coil cleaning:

  • Suction pressure rises to 28 psig (sat. temp. ≈25 °F)
  • Superheat drops to 10 °F
  • Box temperature pulls down to 35 °F within 45 minutes

The fouled coil had been insulating the refrigerant from the box air, driving up superheat and reducing evaporating temperature. No refrigerant was needed — cleaning alone restored full capacity. This illustrates why coil condition must be confirmed before adding refrigerant to a system with high superheat.

Test Your Knowledge
↑ Top