Unit 3 — Refrigeration System Fundamentals & Maintenance
Section 6 — Introduction to System Maintenance

6.5 — Operational Maintenance Checks

A scheduled maintenance visit is not just about fixing faults — it is a systematic inspection of every component that contributes to safe and efficient operation. This lesson covers the standard operational checks performed during a 313A/313D Level 1 preventive maintenance visit, organised by system area.

Jump to

6.5.1 — Airside Checks

Actuators & Dampers

Motorised dampers control outside air, return air, exhaust, and zone air volumes. A sticking or incorrectly calibrated damper can waste enormous amounts of energy by admitting unconditioned air or blocking the required outside air for ventilation.

Belts & Pulleys

Belt-driven fans require tension and alignment checks at every PM visit, and belt replacement on a schedule (typically annually or when showing wear). As covered in 6.4, use the deflection method to verify tension. At each PM:

Coil Condition Checks

Visual coil inspection at each PM allows fouling to be caught before it causes measurable capacity loss. Key checks:

6.5.2 — Electrical Checks

Amperage Measurements

Motor amp draw is one of the most useful single measurements a technician can take. Record amperage for every motor (compressor, condenser fan, evaporator fan, pump) at every PM visit and compare to:

Record keeping: A single amperage reading has limited value; it is the trend over multiple visits that reveals deteriorating components. Always record the ambient conditions (outdoor temperature, indoor load) alongside the reading to make values comparable across visits.

Voltage Measurements

Measure and record supply voltage at the equipment disconnect (not at the panel) with the system running at full load:

Visual Electrical Inspection

Before energising the system at the start of each PM, perform a visual electrical inspection with the disconnect open and locked out:

  1. Check all wire terminations in the disconnect, contactor, control board, and motor terminal box for tightness and corrosion.
  2. Look for discoloured insulation, melted plastic, carbon tracking, or burn marks.
  3. Inspect capacitors for bulging tops, oil leakage, or cracked cases.
  4. Check contactor contacts for pitting; verify contactor pulls in and releases cleanly.
  5. Verify control board for obvious damage, corrosion, or burnt components.
  6. Confirm all safety devices (high-pressure switch, low-pressure switch, freeze stat, flow switch) are wired in and not bypassed.

6.5.3 — Refrigerant & Leak Checks

Electronic Leak Detector Procedure

An electronic leak detector must be used systematically to find small leaks before they result in a measurable charge loss. Heated diode and infrared detectors are the most common types; follow the manufacturer’s warm-up and sensitivity requirements.

  1. Start at the highest-risk locations first: flare fittings, brazed joints at the service valves, condenser coil headers, evaporator coil U-bends.
  2. Hold the probe tip below the refrigerant circuit (refrigerant vapour is heavier than air for most HFCs).
  3. Move the probe slowly (approximately 1 in./second) around each fitting and joint.
  4. When the detector alarms, move the probe away and let it recover, then re-approach from multiple angles to pinpoint the exact leak source.
  5. Mark any leak location found; repair before adding refrigerant.
  6. Recalibrate the detector at fresh air before moving to the next circuit section.

Visual Leak Inspection

Many refrigerant leaks announce themselves visually before they cause measurable charge loss. Look for:

Regulatory note: Canadian regulations require refrigerant leaks above a threshold quantity to be repaired within a specified timeframe. Technicians must document all leak checks and repairs on the equipment service record regardless of leak size.

6.5.4 — Mechanical Checks

Fan Cycling & Controls

Condenser fan cycling controls modulate condenser capacity at low ambient temperatures to maintain adequate head pressure for TXV and metering device operation. At PM:

Lubrication

Motors with grease fittings require periodic lubrication according to manufacturer schedules. Over-lubrication is as harmful as under-lubrication.

Motor & Rotation Check

Verify correct rotation for all fans and pumps at every PM or after any electrical disconnect, motor replacement, or rewiring:

Oil Levels (Open & Semi-Hermetic Compressors)

Open and semi-hermetic compressors have an oil sight glass on the crankcase. Check the oil level with the compressor running at steady state; the oil level should be visible in the lower half to two-thirds of the sight glass. Low oil level indicates:

Check oil colour: clean refrigerant oil is clear to light yellow. Brown or black oil indicates acid contamination or overheating. Test with an oil acid test kit; if acid is present, flush the system and replace the drier and oil charge.

Variable Frequency Drive (VFD) Operation

VFDs control fan and pump motor speeds to match load, providing significant energy savings at part load. PM checks for VFD-driven equipment:

6.5.5 — Condensate Pump & Drain Checks

Condensate Pump

Where gravity drainage is not possible, a condensate pump lifts condensate to a suitable drain. At PM:

  1. Pour water into the pump reservoir until the float triggers and the pump runs; verify water is discharged and the pump shuts off cleanly.
  2. Check the pump reservoir for slime and algae; clean with dilute bleach solution.
  3. Inspect the discharge line for kinks, obstructions, and correct routing to a sanitary drain.
  4. Verify the pump high-level safety switch wiring is intact and connected to the unit’s safety circuit (unit should shut down if the pump fails and reservoir overflows).

Drain Holes & Drain Pans

Drain pans accumulate sludge, algae, and debris that plug the drain outlet even when the main drain line is clear. At each PM:

6.5.6 — Preventive Maintenance Checklist Summary

The following table consolidates all key checks from this lesson into a single reference document. Use it as the basis for a site-specific PM form.

Category Check Item Tool / Method Accept / Action Threshold
Airside Filter pressure drop Manometer Replace when ≥2× clean pressure drop
Supply airflow Anemometer × duct area Within ±10 % of design CFM
Coil condition Visual / flashlight Light through fin pack; no oil staining
Electrical Motor amp draw (each motor) Clamp meter ≤110 % nameplate FLA; stable trend
Supply voltage (L-L, running) True-RMS voltmeter ±10 % of nameplate; <2 % imbalance
Capacitor (ยตF) Capacitor tester Within ±6 % of rated ยตF (run); ±20 % (start)
Visual electrical inspection Visual (LOTO) No burns, discoloration, loose terminations
Refrigerant Electronic leak check Heated diode or IR detector No alarm at any joint or fitting
Suction superheat Gauges + thermometer 8–12 °F (TXV systems); 15–20 °F (fixed orifice)
Subcooling Gauges + thermometer 10–15 °F (verify against manufacturer spec)
Mechanical Belt tension & condition Deflection method Per manufacturer chart; no cracks or glazing
Bearing condition Sound / vibration pen No grinding or rumbling; smooth rotation
Fan rotation direction Visual / airflow check Correct per design; no reverse rotation
Oil level (semi-hermetic) Sight glass Lower to mid sight glass when running; clear colour
Condensate Drain pan & line flush Water test / vac Free flow; no standing water
Condensate pump float test Pour water in reservoir Pump starts, discharges, shuts off cleanly
Controls Damper actuator stroke Visual / DDC command Full travel; position matches signal
Safety device operation Verify wiring continuity All safety switches in circuit; none bypassed

Worked Example — Routine PM Visit: Finding Multiple Issues

A technician performs an annual PM on a 5-ton rooftop unit (R-410A). The following findings emerge from the checklist:

FindingValue / ObservationAction Taken
Filter pressure drop 0.45 in. w.c. (clean = 0.15 in. w.c.) Filter replaced
Condenser coil Heavy cottonwood seed fouling on face Coil washed; head pressure dropped 35 psig after cleaning
Dual-run capacitor 40 ยตF section measures 34 ยตF (15 % low) Capacitor replaced
Condenser fan amp draw 4.8 A vs. 3.5 A FLA nameplate Bearing rough; fan motor replaced
Electronic leak check Alarm at liquid service valve flare Flare retorqued; recheck clear; noted for next visit
Subcooling / Superheat SC 12 °F / SH 10 °F after above repairs Within spec; no refrigerant added

This example illustrates that a single PM visit often reveals several independent issues. Addressing them all at once during a planned visit is far more cost-effective than responding to separate emergency calls after each item causes a failure. All findings, measurements, and parts replaced are documented on the service record and left with the building operator.

Test Your Knowledge
↑ Top